Skip to product information
1 of 9

2456060000 - Dual-Channel Isolated Signal Device for NAMUR Sensors

2456060000 - Dual-Channel Isolated Signal Device for NAMUR Sensors

SKU: SKU: 2456060000 Download PDF

Variant:
  • 2456060000 - Dual-Channel Isolated Signal Device for NAMUR Sensors
Regular price Now $181.68
Regular price BEFORE   $0.00 Sale price Now $181.68
Sold out
IN STOCK
Shipping Available
Free shipping on orders above $1000.* Only on standard purchases of cables and wires.
View full details
Product Information

*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color

Description:

Introducing the ACT20X-HDI-SDO-S family of devices, expertly engineered to transmit digital signals safely from hazardous environments to safer areas With intrinsically safe input circuits, these devices efficiently handle signals from NAMUR sensors in accordance with EN 60947-5-6 standards Additionally, they can connect to potential-free contacts, complete with or without resistor circuitry Available in both single and dual-channel options, these models come equipped with relay or transistor outputs, making them versatile solutions for a variety of applications.

Features and Benefits:

    •Suitable for NAMUR sensors and potential-free contacts.

    •Available in both single and dual-channel configurations.

    •Provides galvanic isolation for safety in explosive atmospheres.

Specifications:

 Depth 113.6 mm
 Height 127.1 mm
 Width 22.5 mm
 Net weight 175 g
 Storage temperature -20 °C...85 °C
 Operating temperature -20 °C...60 °C
 Humidity 0...95 % (no condensation)
 Input frequency <20 Hz
 Input resistance 1 kΩ
 NAMUR supply 8 V DC / 8 mA
 Output signal in case of wire break <0.1 mA
 Continuous current ≤ 2 A AC/DC (safe area, Zone 2 area)
 Max. switching frequency 20 Hz
 Nominal switching voltage ≤ 250 V AC / 30 V DC (safe area)
 Type Relay, 1 NC contact
 Operating altitude ≤ 2000 m
 Supply voltage 19.2…31.2 V DC
 Type of connection PUSH IN
 Insulation coordination EMC standards EN 61326-1
 Insulation voltage 2.6 kV (input / output)
 Rated voltage 300 V

 