Description:

The ACT20X-HUI-SAO-S device offers a reliable solution for transmitting analog signals from hazardous zones to safe areas Engineered with intrinsically safe input circuits, this device prioritizes safety and compliance during its operations.

Features and Benefits:

    •Configuration and diagnosis can be performed using FDT/DTM Software 'WI-Manager'.

    •Mountable in safe area and Zone 2, capable of receiving signals from various hazardous areas.

    •Supports active or passive signal inputs for RTD, TC, potentiometer, voltage, and current with complete electrical isolation.

    •Automatically detects whether a current signal is active or passive.

    •Incorporates cold junction compensation for thermocouple signal inputs for greater accuracy.

    •Features extended self-diagnostics to monitor error events like cable breakage and has a status relay.

    •Indicates operational status and malfunctions through front LEDs.

    •Provides three-way galvanic isolation between input, output, and power supply.

Specifications:

 Depth 113.6 mm
 Height 119.2 mm
 Width 22.5 mm
 Operating temperature -20 °C...60 °C
 Storage temperature -20 °C...85 °C
 Humidity 0...95 % (no condensation)
 Input current 0...20 mA, 4...20 mA
 Input resistance (current) 20 Ω + PTC 50 Ω
 Input resistance (voltage) > 10 MΩ @ 600 mV, 2 MΩ @ 28 V
 Analog output 4...20 mA, loop-powered
 Load resistance (current) <600 Ω
 Protection degree IP20
 Supply voltage 19.2…31.2 V DC
 Weight 202 g
 Power consumption ≤ 2.1 W
 Safety category SIL 2
 Relay lifetime 100000 times

 