Description:

The VPU AC II US 3+1 277/50 is a reliable surge voltage arrester ideal for low voltage applications It provides surge protection across a variety of network systems, including TN-C-S, TN-S, TT, and IT configurations, whether they utilize a neutral or not This device is both ROHS compliant and UL certified, boasting the file number E354261 for added assurance.

Features and Benefits:

    •Compliant with ROHS and other environmental regulations.

    •Available in several colors including orange, black, and blue.

    •Designed for use in operational temperatures ranging from -40 °C to 85 °C.

    •Displays optical functions with a green light indicating normal operation and a red light indicating the need for replacement.

    •Rated for maximum continuous voltages of 350 V and 305 V across different connections.

    •Includes a protection degree of IP20 in the installed state.

    •Features screw connection for wire connection, allowing for a wide range of wire cross-sections.

Specifications:

 Dimensions Depth: 68 mm, Height: 90 mm, Width: 72 mm
 Discharge current I max (8/20µs) N-PE 65 kA
 Rated Voltage U 277 V
 Surge voltage category III
 Ambient temperature (operational), max 85 °C
 Number of poles 4
 Protection level U p at I N (L/N-PE) ≤ 1.75 kV
 Protection level U p at I N (N-PE) ≤ 1.5 kV
 Response time / fallback time ≤ 25 ns
 Electrical data {'Voltage type': 'AC', 'SCCR': '50 kA'}
 Environmental Product Compliance {'RoHS Compliance Status': 'Compliant without exemption', 'REACH SVHC': 'No SVHC above 0.1 wt%'}

 