Skip to product information
1 of 1

General Cable PowrNet® Underground Network Cable 1000MCM 600V Single Copper Conductor EAM Insulation LSZH Jacket

General Cable PowrNet® Underground Network Cable 1000MCM 600V Single Copper Conductor EAM Insulation LSZH Jacket

SKU: SKU:  

Select a gauge:
  • General Cable PowrNet® Underground Network Cable 1000MCM 600V Single Copper Conductor EAM Insulation LSZH Jacket
Length: FT
Enter footage in the box - Cut to one length. Min 1 ft - Max 10000 ft.
Sold out
Shipping calculated at checkout.
Shipping Available
Free shipping on orders above $1000. *Wires and cables only.
View full details
Product Information
PowrNet Underground Network Cable 1000MCM 600V Single Copper Conductor EAM Insulation LSZH Jacket

Complete Cable: General Cable’s PowerNet® 600 V network cables consist of a Class B compressed copper conductor, covered with EAM insulation and a black Low-Smoke, Zero-Halogen (LSZH), flameretardant, lead-free thermoset jacket. All cables are manufactured and tested in accordance with ANSI/NEMA WC70/ICEA S-95-658.

Conductors: Class B compressed copper meeting the requirements of ASTM B8.

Insulation/Jacket: The extruded thermoset, flame-retardant EAM insulation meets the requirements of an EPR Type II (Class E-2) insulation of ANSI/NEMA WC70/ICEA S-95-658. The extruded thermoset black jacket is a Type II Low-Smoke, Zero-Halogen (LSZH), flameretardant, lead-free thermoset polyolefin and meets the requirements of ANSI/NEMA WC70/ ICEA S-95-658.

Features and Benefits: General Cable’s PowrNet 600 V network cable was developed for use in congested urban networks (particularly in duct systems) where high-reliability, easy-to-install low-smoke and -fume cables are needed. This unique cable design provides advantages of a track-resistant, low-smoke and reduced-gas evolution in the event of a fire. These installed performance features are complemented by excellent abrasion and tear resistance properties coupled with a low coefficient of friction which allows easy pulling into existing duct systems. PowrNet is rated 600 V and has a wet and dry conductor operating temperature rating of 90°C.

Applications: General Cable’s PowerNet cable was engineered for use in congested urban secondary network duct and buried systems in wet or dry locations where maximum reliability, ease of installation, and low-smoke cables are required.

Options:
• Multiplexed constructions of 2 to 6 conductors
• Multiplexed with bare ground conductors
• Compact copper conductors
• Tinned copper conductors
• Type RHH/RHW-2 per UL 44
• Type USE-2 per UL 854
• UL OIL RES I (PR 1)
• UL ST-1 limited smoke designation (sizes 1/0 AWG and larger)
• UL “For CT Use” (sizes 1/0 AWG and larger)
• EPR insulation
• 2000 V rating

technical specification:
size awg or kcmil 1000
no. ofwires 61
nom. cond. o.d. 1.117
ins./jacket nom. thkn. inches 0.065 / 0.065
nom. o.d. inches 1.42
approx. weight lb/1000ft(copper) 3088
approx. weight lb/1000ft(total) 3448
ampacity (1)(direct buried) 820
ampacity (1)(in duct (2)) 670