General Cable Uniblend® PVC High Speed Type MV-105 4 Gauge Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
Select gauge from drop-down menu for prices:
- General Cable Uniblend® PVC High Speed Type MV-105 Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 6 Gauge Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 2 Gauge Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 1/0 Gauge Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 2/0 Gauge Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 4/0 Gauge Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 250MCM Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 350MCM Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 500MCM Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 750MCM Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
- General Cable Uniblend® PVC High Speed Type MV-105 1000MCM Three Conductor 115 Mils EPR Copper Tape Shield with Overall PVC Jacket Medium Voltage Power Shielded 5 kV and 8 kV UL
Product Details
Conductor: 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand
Extruded Strand Shield (ESS): Extruded thermoset semi-conducting stresscontrol layer over conductor
Insulation: Lead-free Ethylene Propylene Rubber (EPR) insulation, contrasting in color to the black semi-conducting shield layers
Extruded Insulation Shield (EIS): Thermoset semi-conducting polymeric layer free stripping from insulation
Metallic Shield: 5 mil annealed copper tape with an overlap of 25% Grounding
Conductor: 1 bare grounding conductor may be in contact with metallic shielding tape
Overall Jacket: Low-friction, lead-free, flame-retardant, moistureand sunlight-resistant Polyvinyl Chloride (PVC)
Options:
• STRANDFILL® – blocked conductor. Tested in accordance with ICEA T-31-610
• 3 bare copper ground wires
• Covered ground wires
Applications:
• Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical
• In wet or dry locations when installed in accordance with NEC
• In aerial, direct burial, conduit, open tray and underground duct installations
Features:
• Rated at 105?C
• Low friction for easy pulling
• Excellent heat and moisture resistance
• Outstanding corona resistance
• Flexibility for easy handling
• High dielectric strength
• Low moisture absorption
• Electrical stability under stress
• Low dielectric loss
• Chemical-resistant
• Meets cold bend test at -35?C
• 105°C rating for continuous operation
• 140°C rating for emergency overload conditions
• 250°C rating for short circuit conditions
Compliances:
• National Electrical Code (NEC)
• UL 1072
• ICEA S-93-639/NEMA WC74
• ICEA S-97-682
• AEIC CS8
• UL listed as Type MV-105 for use in accordance with NEC, UL File # E90501
• UL 1685 (70,000 BTU/hr)
• EPA 40 CFR, Part 261 for leachable lead content per TCLP method
• OSHA Acceptable
• RoHS Compliant
Optional Flame Tests: IEEE 1202 (70,000 BTU/hr)/CSA FT4
Packaging:
• Material cut to length and shipped on non-returnable wood reels. Lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit
• Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing
technical specification: | |
cond. size (awg/kcmil) | 4 |
nominal conductor diameter(inches) | 0.22 |
insulation diameter inches(min.) | 0.455 |
insulation diameter inches(max.) | 0.535 |
ground wire(awg) | 6 |
nominal jacket thickness(inches) | 0.080 |
nominal jacket thickness(mm) | 2.03 |
nominal cable(diameter in inches) | 1.39 |
nominal cable(diameter in mm) | 35.31 |
nominal cable(weight in lbs/1000ft) | 1158 |
nominal cable(weight in kg/km) | 1723 |
copper weight(lbs/1000ft) | 616 |
copper weight(kg/km) | 917 |
ampacity(conduit in air (1) in 90?c) | 105 |
ampacity(conduit in air (1) in 105?c) | 120 |
ampacity(underground duct (2) in 90?c) | 115 |
ampacity(underground duct (2) in 105?c) | 125 |
ampacity(tray (3) in 90?c) | 120 |
ampacity(tray (3) in 105?c) | 135 |
catalog number | 15493.400405 |