Type MV-105 power cable has three conductors made of compacted Class B stranded aluminum 1350 or the annealed soft drawn copper in accordance to ASTM specifications. These three conductors are shielded with an extruded thermosetting and semiconducting layer, forming a free stripping from the conductor. The assembly is then insulated with a high dielectric strength EPR compound that is also shielded an extruded thermosetting layer. A metallic shield of non-magnetic copper tape is helically applied round the core with a minimum overlap of 25%. 

Mylar ribbon is applied longitudinally beneath the copper tape shield for phase identity, it is color coded in red, blue and black. A complete cable like Type Mv-105 cable comes with a grounding wire that acts as a neutral path. The grounding wire is made of a stranded bare copper wire in accordance to ICEA, UL and the ASTM specifications. It is laid closely to the metallic shielded conductors and wrapped with a binder tape to hold it firmly to the conductors maintaining the symmetry. This cable is then coated with a strong Air Bag that is crush resistant and jacketed with the Polyvinyl Chloride (PVC).

Standards and Approvals
Medium Voltage 105 cable conforms to the following specification;

1.ICEA S-93-639, NEMA WC74 for Type MV-105
2.IEEE 383 and IEEE 1202
3.CSA Cold Impact (-40C)
4.MSHA CSA FT4
5.ICEA T-29-520

Conductor
This cable features aluminum 1350 conductors or the soft drawn copper conductors. The use of 1350 aluminum series and the soft drawn copper conductors affirms the flexibility aspect of this cable; this is because they are soft and malleable as compared to standard aluminum and copper. The cables is flexible and hence easy to handle especially during installation as compared to stiff and rigid cables.

Insulation
Ethylene Propylene Rubber (EPR) EPROTENAX offers a high dielectric strength which helps in eliminating dielectric loss thus improving the electrical conductivity of the cable. Insulation of the three live conductors keeps the cable safe as well as the user. EPR compound prevents the cable from corrosive chemicals and mechanical damages that may cause distortion to the cable during and after installation. It is a semiconducting compound that does not permit the flow of electrical power therefore will protect the user from electric shocks.

Insulation of the live conductors creates a permanent barrier between them and the grounding conductors. This ensures that they do not get into any form of contact that would lead to power blows, shutting down your equipment. Separation of the live conductors and the neutral wire (grounding conductor) improves the electrical conductivity of Prysmian MV-105 cable.

Jacketing
It is the outer surface of this cable made of Polyvinyl Chloride (PVC) and a high strength Air Bag. The strong Air Bag extruding over the core assembly offers a great mechanical protection to the cable, ensuring that it does not succumb to deformations easily. PVC jacketing layer keeps the cable away from moisture, strong sunlight radiations, flames and corrosive chemicals. This cable can withstand harsh outdoor environmental conditions and you should make it your desired cable of choice and enjoy a long service life.

Applications
Type MV-105 power cable has an operational temperature ratings of -40 degrees Celsius up to 105 degrees Celsius. This shows that it is a dual serving power cable that can perform in both wet and dry locations without difficulty. It is applied in Class 1 and Class 2 installations as a commercial and industrial cable.

conductor insulation
thickness
(mils)
ground wires conductor
diameter
(in)
insulation
diameter
(in)
insulation
shield
diameter
(in)
overall
jacket
diameter (in)
cable
weight (lbs/kft)
minimum
bending radius
(in)
ampacity  (amps) impedance
(micro-
ohms/foot)
prysmian
cable part
number
no. size (a) (b) (c) (d) ‡105°
in duct
‡105°
in air
pos/
negseq
zero seq
5kv 133% & 8kv 100% copper three conductor
8 awg cu 115 3 12 awg 0.135 0.41 0.47 1.36 1267 10 64 66 853 + j53 2023 + j36 QK0570A
6 awg cu 115 3 10 awg 0.170 0.45 0.50 1.43 1484 11 84 88 538 + j49 1631 + j33 QK1570A
4 awg cu 115 2 10 awg 0.215 0.49 0.55 1.53 1759 11 110 115 338 + j45 1325 + j28 QK2570A
2 awg cu 115 3 10 awg 0.266 0.54 0.60 1.75 2187 12 145 154 212 + j42 1134 + j26 QK4570A
1 awg cu 115 3 8 awg 0.299 0.58 0.63 1.78 2567 13 165 180 169 + j40 1045 + j24 QK6570A
1/0 awg cu 115 3 8 awg 0.341 0.62 0.68 1.89 2776 14 190 205 134 + j39 954 + j22 QK8570A
2/0 awg cu 115 3 8 awg 0.376 0.65 0.71 1.97 3104 14 220 240 106 + j37 888 + j21 QK9570A
4/0 awg cu 115 3 7 awg 0.479 0.76 0.82 2.19 4233 16 285 320 67 + j35 752 + j19 QKB570A
250 awg cu 115 3 6 awg 0.522 0.81 0.86 2.30 4869 17 315 355 57 + j34 704 + j18 QKC570A
350 awg cu 115 3 6 awg 0.622 0.91 0.96 2.52 6165 18 380 440 41 + j32 622 + j16 QKD570A
500 awg cu 115 3 5 awg 0.742 1.03 1.08 2.77 7945 20 460 545 29 + j31 548 + j15 QKE570A
750 awg cu 115 3 4 awg 0.917 1.21 1.27 3.25 11505 23 570 685 20 + j30 465 + j13 QKF570A
1000 mcm cu 115 3 3 awg 1.071 1.37 1.42 3.61 14875 26 645 790 16 + j29 413 + j13 QKG570A
15kv 133% copper three conductor
2 awg cu 220 3 10 awg 0.266 0.74 0.80 2.16 2929 16 160 185 212 + j49 898 + j33 QN4570A
1 awg cu 220 3 8 awg 0.299 0.78 0.84 2.23 3263 16 185 210 169 + j46 827 + j30 QN6570A
1/0 awg cu 220 3 8 awg 0.341 0.82 0.88 2.32 3671 17 210 240 134 + j44 763 + j28 QN8570A
2/0 awg cu 220 3 8 awg 0.376 0.85 0.91 2.40 4031 17 235 275 107 + j43 710 + j27 QN9570A
4/0 awg cu 220 3 7 awg 0.479 0.96 1.02 2.62 5207 19 305 360 67 + j40 612 + j24 QNB570A
250 mcm cu 220 3 6 awg 0.522 1.01 1.06 2.73 5821 20 335 400 57 + j39 577 + j23 QNC570A
350 mcm cu 220 3 6 awg 0.622 1.11 1.16 3.03 7511 22 400 490 41 + j37 518 + j21 QND570A
500 mcm cu 220 3 5 awg 0.742 1.23 1.28 3.29 9468 24 485 600 29 + j34 463 + j19 QNE570A
750 mcm cu 220 3 4 awg 0.917 1.41 1.47 3.69 12955 26 585 745 20 + j33 401 + j17 QNF570A
25kv 133% copper three conductor
1 awg cu 320 3 8 awg 0.299 0.98 1.04 2.69 4693 19 185 210 169 + j51 690 + j35 QP4570A
1/0 awg cu 320 3 8 awg 0.341 1.03 1.08 2.83 5394 20 210 240 134 + j49 636 + j33 QP6570A
2/0 awg cu 320 3 8 awg 0.376 1.06 1.12 2.96 5979 21 235 275 107 + j48 594 + j32 QP9570A
4/0 awg cu 320 3 7 awg 0.479 1.16 1.22 3.17 7330 23 305 360 68 + j44 516 + j28 QPB570A
250 awg cu 320 3 6 awg 0.522 1.21 1.27 3.28 7961 23 335 400 57 + j43 489 + j27 QPC570A
350 mcm cu 320 3 6 awg 0.622 1.31 1.37 3.50 9512 25 400 490 41 + j40 443 + j24 QPD570A
500 mcm cu 320 3 5 awg 0.742 1.43 1.49 3.76 11748 27 485 600 29 + j38 400 + j22 QPE570A
750 mcm cu 320 3 4 awg 0.917 1.62 1.67 4.17 15401 30 585 745 20 + j36 352 + j20 QPF570A
1000 mcm cu 320 3 3 awg 1.071 1.77 1.83 4.51 18785 32 660 860 16 + j34 321 + j18 QPG570A
35kv 133% copper three conductor
1/0 awg cu 420 3 8 awg 0.341 1.22 1.27 3.28 6589 23 210 240 134 + j53 561 + j37 QR8570A
2/0 awg cu 420 3 8 awg 0.376 1.25 1.31 3.37 7104 24 235 275 107 + j51 520 + j35 QR9570A
4/0 awg cu 420 3 7 awg 0.479 1.35 1.41 3.59 8525 26 305 360 68 + j47 454 + j31 QRB570A
250 awg cu 420 3 6 awg 0.522 1.40 1.46 3.75 9537 27 335 400 57 + j46 432 + j30 QRC570A
350 mcm cu 420 3 6 awg 0.622 1.50 1.56 3.93 10823 28 400 490 41 + j43 392 + j27 QRD570A
500 mcm cu 420 3 5 awg 0.742 1.62 1.68 4.19 12596 30 485 600 30 + j41 356 + j25 QRE570A
750 mcm cu 420 3 4 awg 0.917 1.81 1.86 4.59 16511 33 585 745 10 + j38 316 + j22 QRF570A
1000 mcm cu 420 3 3 awg 1.071 1.96 2.02 5.00 20547 35 660 860 16 + j37 290 + j21 QRG570A