General Cable ACWU90® 1C 350MCM XLPE AIA PVC Low Voltage Power Armored 600V CSA

General Cable ACWU90® 1C 350MCM XLPE AIA PVC Low Voltage Power Armored 600V CSA

ACWU90 1C 350MCM XLPE AIA PVC Low Voltage Power Armored 600V CSA

Conductor: 4/0 AWG thru 1000 kcmil bare ACM aluminum (8000 series aluminum) compact Class B strand

Insulation:
• Cross-linked Polyethylene (XLPE), Type RW90
• Color-coded: black, marked “SR”

Ground (Bonding) Conductor: The conductor is a concentric serving of solid bare aluminum (ACM) wires applied over the insulation

Armor: Aluminum Interlocked Armor (AIA)

Jacket: ACID-FLAME-CHECK ??® flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black

Applications:
• For exposed and concealed wiring in dry, damp or wet locations
• For use in ventilated, non-ventilated and laddertype cable trays in dry, damp or wet locations
• For direct earth burial (with protection as required by inspection authority)
• For wiring in all hazardous locations when used with certified HL cable glands
• For service entrance installations

Features:
• Rated at 90°C wet or dry
• Excellent crush, oil and chemical resistance
• Provides long service life
• Cost-effective alternative to installations in conduit
• Meets cold bend and impact tests at -40°C

Compliances:
Industry Compliances:
• CSA Standard C22.2 No. 51 and No. 174
• CSA Approval File Number 157657

Flame Test Compliances: CSA FT1 and FT4

Other Compliances:
• Hazardous Location Rating: HL
• OSHA Acceptable

Packaging: For Canadian customers, nominal standard lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for cut to length, lagging, pulling eyes, paralleling and plexing

technical specifications:
cond. size (awg/kcmil) 350
cond. strand 26/.128
nominal conductor o.d.(inches) 0.607
nominal conductor o.d.(mm) 15.418
min. avg. insulation thickness(inches) 0.060
min. avg. insulation thickness(mm) 1.524
nominal diameter (over)(insulation in inches) 0.730
nominal diameter (over)(insulation in mm) 18.542
nominal diameter (over)(armor in inches) 1.120
nominal diameter (over)(armor in mm) 28.448
nominal diameter (over)(cable in inches) 1.240
nominal diameter (over)(cable in mm) 31.496
aluminum weight*(lbs/1000 ft) 329
aluminum weight*(kg/km) 479
net weight( lbs/1000 ft)
743
net weight(kg/km) 1081
90?c ampacity** (30°c ambient) 445
catalog number 11281.016200

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.