Belden Cable 20 and 16 AWG Audio Control and Instrumentation Multi Conductor UnShielded Non Plenum Cable

Belden Cable 20 and 16 AWG Audio Control and Instrumentation Multi Conductor UnShielded Non Plenum Cable

Select gauge from drop-down menu for prices:

Belden Cable 20 and 16 AWG Audio Control and Instrumentation Multi Conductor UnShielded Non Plenum Cable
Belden Cable 20 and 16 AWG Audio Control and Instrumentation Multi Conductor UnShielded Non Plenum Cable

Description:
• 20 and 16 AWG stranded (7x28 and 19x28) tinned copper conductors, conductors cabled, PVC insulation, PVC jacket.

Insulation:
• Material: PVC - Polyvinyl Chloride (20 and 16 AWG)
• Wall Thickness (mm): 0.3048 (20 AWG) and 0.3302 (16 AWG)
• Insulation Resistance: 100 Megaohms/1000 ft. @ 500 V DC

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.8128

Overall Cabling Lay Length and Direction:
• Length (mm): 152.3994
• Twists (twist/m): 6.562

Applications: Applications for multi-conductor cables include computers, communications, instrumentation, sound, control, audio, and data transmission. Each of these cables is designed to protect signal integrity under critical conditions by reducing hum, noise, and crosstalk.

Mechanical Charactertistics (Overall):
• Operating Tempeature Range: -20°C To +80°C
• Non-UL Temperature Rating: 90°C
• Bulk Cable Weight: 93.905 Kg/Km
• Max. Recommended Pulling Tension: 592.500 N
• Min. Bend Radius/Minor Axis: 76.200 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CM
• NEC Articles: 800
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Inductance (μH/m): 1.04336 (20 AWG)
• Nom. Inductance (μH/m): 0.639795 (16 AWG)
• Nom. Capacitance Conductor to Conductor (pF/m): 65.62 (1 Freq. MHz , 20 AWG)
• Nom. Capacitance Conductor to Conductor (pF/m): 98.43 (1 Freq. MHz , 16 AWG)
• Nom. Capacitance Cond. to Other Cond. & Ground (pF/m): 118.116 (20 AWG)
• Nom. Capacitance Cond. to Other Cond. & Ground (pF/m): 177.174 (16 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 33.6303 (20 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 13.3537 (16 AWG)
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 3.2 Amps/Conductor @ 25°C (20 AWG)
• Max. Recommended Current: 5.6 Amps/Conductor @ 25°C (16 AWG)

Flame Test:
• UL Flame Test: UL1685 UL Loading

Plenum/Non-Plenum:
• Plenum (Y/N): No

awg # conductors stranding no.of
conductors
conductor
material
outer shield -
material
overall cable-
nominal
dia. (mm)
belden cable
part
number
20 and 16 3 and 3 7x28 and 19x28 6 tinned copper unshielded 7.493 9686

QUESTIONS & ANSWERS