General Cable PowrServ® CDC 1 1/4 inches Underground Distribution Secondary Combined Duct & Cable Secondary Cable Installed in Extruded High-Density Polyethylene Duct
Select gauge from drop-down menu for prices:
- General Cable PowrServ® CDC Underground Distribution Secondary Combined Duct & Cable Secondary Cable Installed in Extruded High-Density Polyethylene Duct
- General Cable PowrServ® CDC 1 1/2 inches Underground Distribution Secondary Combined Duct & Cable Secondary Cable Installed in Extruded High-Density Polyethylene Duct
- General Cable PowrServ® CDC 2 inches Underground Distribution Secondary Combined Duct & Cable Secondary Cable Installed in Extruded High-Density Polyethylene Duct
Complete Assembly: PowrServ® CDC® Combined Duct & Cable consists of insulated conductor(s) factory installed in a black High-Density Polyethylene (HDPE) conduit. The HDPE conduit is extruded directly over any prior-made single or plexed 600 volt cable assembly.
Complete Cable: All underground distribution cables in PowrServ CDC are manufactured and tested in accordance with applicable industry standards and/or individual customer specifications. See the appropriate catalog section for a complete cable description.
Conduit: The high-density polyethylene EPEC-A conduit is manufactured and tested in accordance with NEMA Standard TC7, “Smooth-wall Coilable Electrical Polyethylene Conduit.”
Applications: PowrServ CDC Combined Duct & Cable offers an economical alternative to pulling cable in previously installed short lengths of duct joined with sleeve couplings. The inherent construction advantages and versatility of the PowrServ CDC design are ideally suited for underground secondary distribution systems.
Features and Benefits: In addition to the initial labor savings achieved from installation of cable and conduit in a single operation, cable replacement costs and ground disruption are significantly less for the PowrServ CDC cable system. Tough, yet light and flexible, high-density polyethylene conduit provides ease of installation and high impact resistance for cable protection.
Options:
• EPEC-B, EPEC-40 or EPEC-80 Smooth-Wall Coilable Electrical Polyethylene Conduit to NEMA TC7
• Gray or red color
• Extruded red stripes
technical specification: | |
nominal conduit size (inches) | 1 1/4 |
minimum i.d. (inches) | 1.408 |
o.d. (± 0.012") (inches) | 1.660 |
minimum inside area (sq.inches) | 1.557 |
approx. weight (lb/1000ft) | 240 |
minimum* wall thickness (inches) | 0.100 |
minimum bend radius (inches) | 18 |
max. total CSA of cond. (sq. inches in 53% fill 1C) | 0.825 |
max. total CSA of cond. (sq. inches in 31% fill 2C) | 0.483 |
max. total CSA of cond. (sq. inches in 40% fill 3C) | 0.623 |
max. total CSA of cond. (sq. inches in 40% fill 4C) | 0.623 |
max. diameter of each cond. (inches in 1C) | 1.025 |
max. diameter of each cond. (inches in 2C) | 0.555 |
max. diameter of each cond. (inches in 3C) | 0.514 |
max. diameter of each cond. (inches in 4C) | 0.445 |