*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Conductors: Class B Compressed Unilay (1 AWG to 4/0 AWG) or Compressed Round aluminum alloy 1350 per ASTM.
Phase Insulation: Extruded thermosetting cross-linked black, sunlight resistant polyethylene.
Neutral Insulation: Extruded thermosetting cross-linked black, sunlight resistant polyethylene with three extruded yellow stripes (120° apart) for neutral identification.
Assembly: For multiple cable assemblies, one, two, or three phase conductors with one neutral twisted together.
Cable Markings: Sequential footage markings on one phase conductor. Phase identification surface printed in white ink: 1/C - “Phase A”, 1/C - “Phase B”, 1/C - “Phase C”, as applicable.
Applications: Secondary UD Power Cable, with aluminum conductors and a single-layer cross-linked polyethylene insulation that is formulated for a balance of flexibility and mechanical toughness.
Options:
• Strandseal®
• Copper or Series 8000 Aluminum Conductor(s)
• Paralleled
• Solid Black Neutral
Installation:
• Direct Buried
• Underground Duct
• Wet Locations
• Dry Locations
• Utility Secondary
• Industrial
• Underground Service Entrance
Specifications and Ratings:
• UL- UL 854 Type USE-2
• ICEA- ICEA S-105-692
• REA- REA U-2
• For 90°C Wet or Dry Operation.
| technical specifications: | |
| phase conductor | 3/0 awg al |
| code name | Tufts |
| phase insulation thickness (mils) | 80 |
| phase conductor diameter (in) - (a) | 0.443 |
| outside diameter (in) - (b) | 0.61 |
| cable weight (lbs/kft) | 215 |
| minimum bending radius (in) | 3 |
| † ampacity (amps) -90°c in duct | 180 |
| † ampacity (amps) -90°c direct buried | 260 |
| prysmian cable part number | Q0S300A |