Description:
Introducing the weFlux² pressure sensors, featuring an advanced measuring cell that integrates a temperature sensor This innovative design allows users to monitor both relative pressure and the temperature of various media Depending on your specific needs, you can opt for either two switching outputs or a combination of one switching output and one analog output for delivering measurement data Additionally, the weFlux² sensors excel in customization, enabling you to adjust sensor parameters, filtering options, output functions, and select the unit of measurement—be it bar, PSI, or Pascal—to suit your application perfectly.
Features and Benefits:
•Pressure and temperature measurement with a single sensor.
•Individual parameter configuration via IO-Link 1.1.
•Compact, laser-welded stainless steel 316L housing.
•Temperature-compensated pressure measurement.
Specifications:
| Measuring Range | 0 ... 0.25 bar |
| Measurement Type | relative |
| Maximum overload pressure | 1 bar |
| Bursting pressure | 1.5 bar |
| Medium | Liquids, gases |
| Temperature Measurement Range | -40 ... 125 °C |
| Response time (t90) Temp | < 1 s |
| Pressure response time (t90) | < 10 ms |
| Temperature Measurement Accuracy | < ± 1 °C |
| Measuring error (total) | ± 0.5 % |
| Hysteresis | < ± 0.1 % |
| Linearity Deviation | < ± 0.5 % |
| Zero-point error | < ± 0.1 % |
| Repeat Accuracy | < ± 0.1 % |
| Temperature coefficient zero-point | <± 0,05% /10K |
| Temperature coefficient range | <± 0,05% /10K |
| Environmental conditions | |
| Temperature of medium | -40 ... 125 °C |
| Ambient temperature | -25 ... 80 °C |
| Storage temperature | -25 ... 80 °C |
| EMC | DIN EN 61326-2-3 |
| Shock resistance per DIN IEC 68-2-27 | 50 g / 11 ms |
| Vibration resistance per DIN IEC 60068-2-6 | 10 g (10...2000 Hz) |
| Supply Voltage | 12 ... 32 V DC |
| Current Consumption (Ub = 24 V) | < 15 mA |
| Number of Switching Outputs | 2 |
| Switching Output / Switching Current | 100 mA |
| Switching Output Voltage Drop | < 1.5 V |
| Number of analog outputs | 1 |
| Analog Output | 4...20 mA |
| Signal source | Pressure |
| Resolution | > 11 bit |
| Current Output Load Resistance | < 500 Ohm |
| Voltage output load resistance | > 1 kOhm |
| Interface | IO-Link V1.1 |
| Short Circuit Protection | yes |
| Reverse Polarity Protection | yes |
| Protection Class | III |
| Setting Method | IO-Link |
| Sensor element | Ceramic membrane |
| Housing Material | Stainless steel, V4A (1.4404/316L) |
| Material in contact with media | Stainless steel, V4A (1.4404 / 316L), Rubber, FKM, Ceramic |
| Degree of Protection | IP65 |
| Connection | M12 × 1; 4-pin |
| Process Connection | G3/4"; front |
| Seal material | Fluororubber, FKM |
| MTTFd (EN ISO 13849-1) | 1,157.11 a |
| Adjustable parameters | Analog output 0...10 V, 4...20 mA, Signal source Pressure, Temperature |
| Output | Analog Output |