FX1Q001 - Customizable Pressure Sensor with Temperature Features and IO-Link
FX1Q001 - Customizable Pressure Sensor with Temperature Features and IO-Link
SKU: SKU: FX1Q001 Download PDF
- FX1Q001 - Customizable Pressure Sensor with Temperature Features and IO-Link
- FX1Q001 - Customizable Pressure Sensor with Temperature Features and IO-Link
Couldn't load pickup availability

*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Description:
Introducing the weFlux² pressure sensors, featuring a cutting-edge measuring cell that incorporates an integrated temperature sensor This innovative design enables the devices to accurately gauge both relative pressure and the temperature of various media You can customize your setup with options for either two switching outputs or a combination of one switching output and one analog output for displaying the measured data.
With weFlux², enjoy unparalleled flexibility in configuring parameters Adjust sensor settings, filtering, output functions, and select your preferred measurement unit—bar, PSI, or Pascal—to match your specific application requirements.
Features and Benefits:
•Pressure and temperature measurement with a single sensor.
•Individual parameter configuration via IO-Link 1.1.
•Compact, laser-welded stainless steel 316L housing.
•Temperature-compensated pressure measurement.
Specifications:
| Measuring Range | -1 ... 1 bar |
| Measurement Type | relative |
| Maximum overload pressure | 5 bar |
| Bursting pressure | 7.5 bar |
| Medium | Liquids, gases |
| Temperature Measurement Range | -40 ... 125 °C |
| Response time (t90) Temp | < 1 s |
| Pressure response time (t90) | < 10 ms |
| Temperature Measurement Accuracy | < ± 1 °C |
| Measuring error (total) | ± 0.5 % |
| Hysteresis | < ± 0.1 % |
| Linearity Deviation | < ± 0.5 % |
| Zero-point error | < ± 0.1 % |
| Repeat Accuracy | < ± 0.1 % |
| Temperature coefficient zero-point | <± 0,05% /10K |
| Temperature coefficient range | <± 0,05% /10K |
| Temperature of medium | -40 ... 125 °C |
| Ambient temperature | -25 ... 80 °C |
| Storage temperature | -25 ... 80 °C |
| EMC | DIN EN 61326-2-3 |
| Shock resistance per DIN IEC 68-2-27 | 50 g / 11 ms |
| Vibration resistance per DIN IEC 60068-2-6 | 10 g (10...2000 Hz) |
| Supply Voltage | 12 ... 32 V DC |
| Current Consumption (Ub = 24 V) | < 15 mA |
| Number of Switching Outputs | 2 |
| Switching Output / Switching Current | 100 mA |
| Switching Output Voltage Drop | < 1.5 V |
| Number of analog outputs | 1 |
| Analog Output | 4...20 mA |
| Signal source | Pressure |
| Resolution | > 11 bit |
| Current Output Load Resistance | < 500 Ohm |
| Voltage output load resistance | > 1 kOhm |
| Interface | IO-Link V1.1 |
| Short Circuit Protection | yes |
| Reverse Polarity Protection | yes |
| Protection Class | III |
| Setting Method | IO-Link |
| Sensor element | Ceramic membrane |
| Housing Material | Stainless steel, V4A (1.4404/316L) |
| Material in contact with media | Stainless steel, V4A (1.4404 / 316L), Rubber, FKM, Ceramic |
| Degree of Protection | IP65 |
| Connection | M12 × 1; 4-pin |
| Process Connection | G3/4"; front |
| Seal material | Fluororubber, FKM |
| MTTFd (EN ISO 13849-1) | 1,157.11 a |
| Adjustable parameters | Analog output 0...10 V, 4...20 mA, Signal source Pressure, Temperature |
| Output | Analog Output |
| Push-pull | yes |
| PNP | yes |
| IO-Link | yes |
| Circuit | NC, NC/NO, NO |
| Other parameters | 2 switching points |