500' 400 MCM THHN/THWN-2 Aluminum Cable PVC Insulation Nylon Jacket 600V

500' 400 MCM THHN/THWN-2 Aluminum Cable PVC Insulation Nylon Jacket 600V

SKU: SKU: NES28801X-18   Download PDF

Color
Select a Variant:
  • 500' 400 MCM THHN/THWN-2 Aluminum Cable PVC Insulation Nylon Jacket 600V
Qty:
Regular price Now $1,480.00   Web pricing policy
Regular price BEFORE   Sale price Now $1,480.00 Web pricing policy
Sold out
Shipping calculated at checkout.
IN STOCK
Shipping Available
Free shipping on orders above $1000. *Wires and cables only.
View full details
Product Information

Also Known As:

400 thhn cable, 400 thwn cable, 400 mcm thhn cable, 400 mcm thwn cable, 400 thhn aluminum, 400 pvc insulated, 400 pvc insulated wire, 400 pvc insulated aluminium wire, 400 pvc sheathed cable, 400 pvc flexible cable.

Conductors:

THHN / THWN-2 / T90 conductor is a compact soft drawn bare 8000 series aluminum, with Class B stranding per ASTM. Stranded conductors reduce power loss and are also easier to use in applications where flexibility is vital. 

Insulation:

THHN / THWN-2 / T90 has abrasion, heat, moisture, oil, and acid alkaline resistant polyvinyl chloride (PVC) insulation.

Jacket:

THHN / THWN-2 / T90 cables have a clear abrasion, heat, sunlight, moisture resistant, and low coefficient of friction nylon jacket. Standard stock colors include: black, red, blue, white, brown, orange, yellow, gray, purple, and green.

Compatible with Manufacturer

Priority Wire & Cable : 400-01AL-THHN
Classic Wire & Cable : A400-01THHN
Southwire : Black : 56267701
Blue : 56277899
Brown : 56278101
Gray : 56278301
Green : 56269999
Orange : 56278201
Purple : 57337699
Red : 56277699
White : 56277999
Yellow : 56278001

Resources


Applications
The electrical wires known as THHN / THWN-2 / T90 cables are primarily used for power distribution, in both wet and dry places, with ambient temperatures not exceeding 90°C. The voltage rating of this electrical wire, XHHW-2 cable, is 600V.
Features
Standards:

• UL standard 83, 1685, CUL

• CSA C22.2 No. 75

• 1/0 & larger are rated for CT use

• Requirements of the National Electrical Code

• NEMA WC-70 construction requirements

• ASTM standards B 800, B 801, B836

• Federal Specification AA-59544

• Sunlight resistant

• RoHS Compliant

Allowable Ampacity for 400 MCM THHN/THWN-2 Aluminum Cable PVC Insulation Nylon Jacket 600V at 90°C: 305 Amps
Specifications
• Size AWG: 400

• Stranding: 35

• Conductor Diameter Inches: 0.657

• Insulation Thickness Inches: 0.65

• Jacket Thickness Inches: 0.008

• O.D. Inches: 0.795

• New Weight lb/1000FT: 453 lbs

• Ampacity at 90°C: 305 Amps