Product Information
Conductor: 1 AWG thru 500 kcmil coated annealed copper,
bunched wires, rope-lay-stranded per ASTM B172
Extruded Strand Shield (ESS): Extruded thermosetting semi-conducting stress
control layer over conductor
Insulation: Ethylene Propylene Rubber (EPR) insulation
colored for contrasting with black
conducting layer
Insulation Shield: A flexible coated copper/textile braid shield is
applied over a non-conducting overlapped tape
Ground-Check Conductor:
• Coated copper, specially stranded to provide
extensibility without sustaining tensile load,
thereby providing maximum resistance to flex
fatigue
• Insulated with high-strength polypropylene and
placed in the center interstice
Grounding Conductors: Three coated copper, rope-lay-stranded per
ASTM B172 in contact with the flexible braid
shield
Jacket: Reinforced, two-layer, extra-heavy-duty, leadcured
Chlorinated Polyethylene (CPE)
Jacket Marking: GENERAL CABLE® ANACONDA® BRAND
(SIZE) 3/C TYPE SHD-CGC 5000 VOLTS
P-7K-102-046 MSHA
Options:
• Colored jackets are available
• TPU (Thermoplastic Polyurethane) jacket
• Anamaxx® jacket
Applications:
• Designed for use as a trailing cable on AC
mining equipment:
- Where maximum safety is mandatory,
including underground mining machines where
induced voltages in an unbalanced grounding
system could be hazardous
- On low- and medium-voltage AC circuits
where shielding is desired or required
Features:
• Flexible insulation shield provides shock hazard
protection
• Symmetrical grounding system does not
produce induced voltages when operating in a
balanced 3-phase system
Anaconda® Brand Type SHD-CGC Power, Shielded Round
Portable w/Extensible Ground-Check, EPR/CPE
5000 Volts, 90°C, Three Conductor
• Excellent heat, moisture, steam, oil, chemical
and radiation resistance
• Flexible for easy handling
• Resists cutting, impact, abrasion, flame
and sunlight
• Excellent thermal stability and physical
properties over a broad temperature range
• Two-layer jacket is reinforced to provide
maximum protection from mechanical
damage —the cause of most portable
cable failures
Compliances:
• ICEA S-75-381 Portable and Power Feeder
Cables for use in mines and similar applications
• Meets flame test requirements and is accepted
for listing by MSHA
• Approved by the Pennsylvania Department of
Environmental Protection
Packaging: Material cut to length and shipped on nonreturnable
reels
| cond. size (awg/ kcmil) |
no. of cond. |
cond. strand |
nominal insulation thickness |
grd. cond. size(awg) |
grd- check cond. size(awg) |
nominal jacket thickness |
nominal cable 0.d. |
copperweight |
netweight
|
ampacity |
catalognumber
|
|||||
| inches | mm | inches | mm | inches | mm | lbs/
1000 ft
|
kg/km
|
lbs/1000 ft
|
kg/km
|
|||||||
| 1 | 3 | 259 | 0.110 | 2.8 | 7 | 16 | 0.205 | 5.2 | 1.98 | 50.29 | 1211 | 1802 | 2843 | 4231 | 184 | 16299.060100 |
| 1/0 | 3 | 259 | 0.110 | 2.8 | 6 | 16 | 0.220 | 5.6 | 2.10 | 53.34 | 1473 | 2192 | 3319 | 4939 | 211 | 16299.065100 |
| 2/0 | 3 | 329 | 0.110 | 2.8 | 5 | 16 | 0.220 | 5.6 | 2.20 | 55.88 | 1879 | 2796 | 3965 | 5900 | 243 | 16252.530102 |
| 3/0 | 3 | 413 | 0.110 | 2.8 | 4 | 16 | 0.235 | 6.0 | 2.36 | 59.94 | 2279 | 3391 | 4729 | 7037 | 279 | 16299.065300 |
| 4/0 | 3 | 532 | 0.110 | 2.8 | 3 | 16 | 0.235 | 6.0 | 2.50 | 63.50 | 2838 | 4223 | 5626 | 8372 | 321 | 16299.065400 |
| 250 | 3 | 608 | 0.120 | 3.0 | 2 | 16 | 0.250 | 6.4 | 2.69 | 68.33 | 3406 | 5068 | 6488 | 9655 | 355 | 16299.066000 |
| 300 | 3 | 741 | 0.120 | 3.0 | 1 | 16 | 0.250 | 6.4 | 2.81 | 71.37 | 3698 | 5503 | 7141 | 10627 | 398 | 16299.066100 |
| 350 | 3 | 851 | 0.120 | 3.0 | 1 | 16 | 0.265 | 6.7 | 2.95 | 74.93 | 4287 | 6379 | 8061 | 11996 | 435 | 16299.066200 |
| 500 | 3 | 1221 | 0.120 | 3.0 | 2/0 | 16 | 0.280 | 7.1 | 3.31 | 84.07 | 6500 | 9673 | 11514 | 17134 | 536 | 16299.066500 |