Superior Essex Cable 2 AWG 4 Conductor XLPE/PVC 600V Power Type TC-ER Unshielded Cable E3BFA-021B04CE00

Superior Essex Cable 2 AWG 4 Conductor XLPE/PVC 600V Power Type TC-ER Unshielded Cable E3BFA-021B04CE00

Select gauge from drop-down menu for prices:

Superior Essex Cable 2 AWG 4 Conductor XLPE/PVC 600V Power Type TC-ER Unshielded Cable E3BFA-021B04CE00

Product Details

The Superior Essex XLPE/PVC, 600V Power, Type TC-ER Cable consist of fully annealed bare copper Class B stranded conductors, covered with Cross-linked Polyethylene (XLPE) insulation, unshielded and black PVC jacket. These cables are used in industrial power.

Features:
• Rated at 90°C wet or dry
• Ripcord (for jackets with thicknesses of 60-mils or less)
• Excellent sunlight resistance
• Smallest OD available for suitable applications
• Meets cold bend test at -25°C

Specifications:
Conductor Count: Available in 3 or 4 conductors

Conductor: Fully annealed bare copper Class B compressed strand per ASTM B8

Gauge Sizes: Available in 12 AWG through 750 kcmil

Insulation: Cross-linked Polyethylene (XLPE)
• All gauges are type XHHW-2

Color Coding: Per ICEA S-58-679 Method 4 or Method 1, Table E-1 (K-1) or E-2 (K-2); additional color coding options available

Fillers: Non-hygroscopic fillers, as necessary to obtain a round finish conductor

Ground Conductor: Uninsulated bare copper ground

Jacket: Polyvinyl Chloride (PVC)

Jacket Marking: 00000 FT SUPERIOR ESSEX XXAWG XX/C XHHW-2 PVC JKT 600V 90C WET OR DRY TYPE TC-ER (UL) SUN RES DIR BURIAL MADE IN USA MMDDYYYY

Packaging: Non-returnable wood reels in a variety of lengths and dimensions

Performance Compliances: 
• ASTM B8
• ASTM B33
• UL® 44
• UL 1277
• UL 1685 (flame compliance)
• ICEA S-95-658/NEMA WC70
• NEC

Other Compliances: 
• EPA 40 CFR, Part 261
• OSHA
• RoHS-compliant/RoHS 2-compliant
• REACH-compliant

Applications:
• In conduit, duct, free air, raceways and direct burial, primary installations include cable trays, and outdoor  locations
• In wet or dry locations
• Approved for Class I, Div. 2 industrial hazardous locations per NEC
• Permitted for Exposed Run (ER) use in accordance with NEC for 3 or more conductors

technical specification:
conductor size awg/kcmil 2
conductor count 4
ground size awg 6
nominal insulation thickness¹ in (mm)
0.045 (1.14)
nominal jacket thickness¹ in (mm)
0.080 (2.03)
nominal overall diameter¹ in (mm) 1.11 (28.2)
nominal net weight¹ lbs/kft (kg/km) 1,205 (1,795)
superior essex cable part number E3BFA-021B04CE00

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question