Single conductor cable with stranded copper conductor, extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX® EPR insulation, thermosetting semiconducting insulation shield, helically applied bare copper tape shield, separator tape, foamed polymeric Air Bag™ layer for superior mechanical protection, a Drylam® layer consisting of a longitudinally applied aluminum tape and an extruded oil and hydrocarbon resistant polymer, and overall non-leaded sun resistant PVC jacket.
Specifications:
• CSA -CSA C68.10
• CSA - C22.2 No.0.3
• CSA - C22.2 No. 230
Ratings:
• Cold Impact/Bend Test (-40°C) 105°C
• Sunlight Resistant FT4
• TC (1/0 AWG and Larger)
Conductor: Class B Compact concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Natural high dielectric strength EPROTENAX® EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Helically applied non-magnetic copper tape(s) over the insulation shield followed by a separator tape.
Mechanical Protection: High strength and high crush resistant Air Bag™ Layer extruded over the core.
Chemical Protection: A layer of Drylam® which consists of an aluminum tape a chemical resistant extruded polymer layer is applied.
Jacket: Sunlight resistant polyvinyl chloride (PVC), non-leaded jacket.
| technical specification | |
| conductor size | 250 MCM AL |
| insulation thickness (mils) | 320 |
| conductor diameter (mm) (A) | 13.26 |
| insulation diameter (mm) (B) | 30.84 |
| insulation shield diameter (mm) (C) | 32.31 |
| overall jacket diameter (mm) (D) | 43.00 |
| cable weight (lkg/km) | 1936 |
| minimum bending radius (mm) | 516 |
| ampacity in air and cable tray‡105°c | 380 |
| impedance in air and cable tray (μω/m) pos/neg seq | 321 + j229 |
| impedance in air and cable tray (μω/m)zero seq | 1714 + j88 |
| prysmian cable part number | CODE DNE |