Prysmian and Draka Cable Low Voltage AIRGUARD harsh environments heavy industrial offshore VFD 600 Volt Power Cable

Conductor: Class B stranded bare, soft drawn copper circuit conductors

Insulation: Heat and moisture resistant cross-linked polyethylene (XLPE) meeting the requirements of UL-44 for Type XHHW-2 conductors

Fillers: Extruded filler belt 

Ground Wires: Class B stranded bare, soft drawn copper ground conductors

Emi Shield: Metallic tape provides 100% coverage

Polmeric Aromor/Enviromental Barrier: Foamed polymeric AIRBAG™ layer affords superior mechanical & environmental protection of the cable core

Outer Sheath:
 Heat, moisture, hydrocarbon, and sunlight resistant thermoplastic

Description:
Prysmian’s Low Voltage AIRGUARD™ Power Cables are primarily designed for applications in the harsh environments found in the heavy industrial and offshore markets. Its rugged polymeric AIRBAG™ armor and chemical barrier protection package makes it the ideal cable choice for tough harsh environmental conditions. AIRGUARD™ provides the solution to the deficiencies often encountered with MC-HL cables including armor breakage encountered during installation and in applications requiring recurring bending after installation, as well as poor performance in areas of high vibration (e.g. motor connections). It also provides a safer and lower installed cost alternative to MC-HL cables due to faster, “No Knife/ No Saw” cable preparation and substantially reduced cost of cable glands

Specifications: 

ASTM B3 & ASTM B8
Class B Soft Drawn Concentric Lay Stranded Bare Copper Conductors

ICEA S-82-658 (NEMA WC70)
Power Cable Rating

UL 44 (XHHW-2) 600V
XHHW-2 Multiple Conductors Direct Buried Sunlight Resistant O il Resistant IEEE 1202/FT-4 Flame Retardant

UL 1277 NEC Article 336.10(7) 
TC-ER Exposed Run Rating 

UL 2225 NEC Article 501.10(A)(2)(3) 
TC-ER- HL Class I Division 1 Hazardous Locations

NEC Article 505.15(B)(1)(i) 
TC-ER-HL Class I Zone 1 Hazardous Locations

CSA 22.2 No. 03
-40oC/ -35oC Cold Bend/ Cold Impact

MSHA
Mine Safety & Health Administration

number
and circuit
conductor
size
number of
grounding
conductor
insulation
thickness
ground
wires
size
conductor
diameter
nominal
overall
insulation
(od)
nominal
overall
cable
(od )
nominal
cable
weight
minimum
bending
radius
    ‡
ampacity
(amps)
gland,
explosion
proof, class 1
division 1,
barrier type
prysmian and
draka cable
part number
# mils awg inches inches inches lbs/mft inches ‡90°c
3/c #14 awg 3 30 18 awg 0.071 0.135 0.630 247 7.5 15 424bt03 394039
3/c #12 awg 3 30 16awg 0.089 0.153 0.670 296 8.1 20 424bt03 394041
3/c #10 awg 3 30 14 awg 0.113 0.177 0.725 364 8.7 30 424bt03 394043
3/c #8 awg 3 45 14 awg 0.142 0.238 0.905 544 10.9 55 424bt04 394045
3/c #6 awg 3 45 12 awg 0.178 0.274 0.990 696 11.9 75 424bt04 394046
3/c #4 awg 3 45 12 awg 0.225 0.321 1.095 898 13.2 95 424bt15 *394047
3/c #2 awg 3 45 10 awg 0.283 0.379 1.225 1236 14.7 130 424bt15 *394048
3/c #1/0 mcm 3 55 10 awg 0.360 0.476 1.445 1719 17.3 170 424bt06 *394049
3/c #2/0 mcm 3 55 10 awg 0.402 0.518 1.540 2017 18.5 195 424bt06 *394050
3/c #4/0 kcm 3 55 8 awg 0.512 0.63 1.83 3450 13 260 424bt07 *20127515
3/c #250 kcm 3 65 8 awg 0.558 0.70 1.98 4024 14 290 424bt07 *20127514
3/c #350 kcm 3 65 7 awg 0.661 0.80 2.22 5312 16 350 424bt08 *20127942
3/c #400 kcm 3 65 7 awg 0.706 0.85 2.41 6008 17 380 424bt09 *20127513
3/c #500 kcm 3 65 6 awg 0.789 0.93 2.53 7194 18 430 424bt09 *20147056
3/c #750 kcm 3 80 5 awg 0.973 1.09 3.02 10518 22 535 -------- *306451a