Helukabel 26 AWG 4 Pairs PAAR-TRONIC-CY-CY LiYCY-CY EMC-Preferred Type Meter Marking Bare Copper Conductor Cable 21067

Helukabel 26 AWG 4 Pairs PAAR-TRONIC-CY-CY LiYCY-CY EMC-Preferred Type Meter Marking Bare Copper Conductor Cable 21067

Select gauge from drop-down menu for prices:

Helukabel 26 AWG 4 Pairs PAAR-TRONIC-CY-CY LiYCY-CY EMC-Preferred Type Meter Marking Bare Copper Conductor Cable 21067
Helukabel 26 AWG 4 Pairs PAAR-TRONIC-CY-CY LiYCY-CY EMC-Preferred Type Meter Marking Bare Copper Conductor Cable 21067

Technical Data:
• Special PVC data transmission cable adapted to DIN VDE 0812 and 0814

Temperature Range:
• flexing -5°C to +80°C
• fixed installation -40°C to +80°C

Operating Peak Voltage:
• (not for heavy current installation purposes)
• 0,14 mm² = max. 350 V
• ≥ 0,25 mm² = max. 500 V

Test Voltage:
• 0,14 mm² = 1200 V
• ≥ 0,25 mm² = 2000 V

Breakdown Voltage:
• 0,14 mm² = 2400 V
• ≥ 0,25 mm² = 4000 V

Mutual Capacitance:
core/core:
• 0,14 mm² = 147 pF/m
• 0,25 mm² = 152,5 pF/m
core/screen:
• 0,14 mm² = 147 pF/m
• 0,25 mm² = 263 pF/m

Impedance:
• 0,14 mm² = 536 Ohm/1 kHz/20°C
• 0,25 mm² = 396 Ohm/1 kHz/20°C

Coupling: 250 pF/100 m/1 kHz

Screen Resistance:
• 0,14 mm² = 36 Ohm/km
• 0,25 mm² = 18 Ohm/km

Attenuation:
• 0,14 mm² = 3,6 dB/1 kHz/km
• 0,25 mm² = 2,2 dB/1 kHz/km

Coupling resistance:
• max. 250 Ohm/km

Minimum Bending Radius:
• flexing 12x cable Ø
• fixed installation 6x cable Ø

Radiation Resistance:
• up to 80x106 cJ/kg (up to 80 Mrad)

Cable Structure:
• Bare copper, fine wire conductors, to DIN VDE 0295 cl.5
• Conductor construction: 0,14 mm² = 18x0,1 mm, 0,25 mm² = 14x0,15 mm, 0,34 mm² = 7x0,25 mm
• Core insulation of special PVC compound type TI2 to DIN VDE 0207-363-3 / DIN EN 50363-3
• Core identification (pair) to DIN 47100
• Cores stranded in pairs with optimal lay-length
• Pairs screened individually, tinned copper, coverage approx. 85%
• Special PVC coating over individual screened pairs all pairs-CY stranded together
• Foil wrapping
• Overall braid-screening, tinned copper coverage approx. 85%
• Outer sheath of special PVC compound type TM2 to DIN VDE 0207-363-4-1/DIN EN 50363-4-1
• Sheath colour grey (RAL 7001)
• With meter marking

Properties:
• Extensively oil resistant, oil-/ chemical Resistance - see table Technical Informations
• The materials used in manufacture are cadmium-free and contain no silicone and free from substances harmful to the wetting properties of lacquers

Tests:
• PVC self-extinguishing and flame retardant acc. to DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent DIN VDE 0472 part 804 test method B)

Note:
• As of 0,75 mm² cross-sec. see type EDV-PiMF-CY.
• AWG sizes are approximate equivalent values. The actual cross-section is in mm².

Application:
As a control and signal cable in electronics, instrumentation and control technology. Interference free transmission of data signals from peripheral devices to information storage. Excellent connecting cable for mixing console, studio equipment, measuring and control technology. Reliable in process control, in machining centers and safety engineering systems. These cables with copper screening are suitable for interference free data and signal transmission in the measurement, control and regulation technology.
EMC = Electromagnetic compatibillity
To optimize the EMC features we recommend a large round contact of the copper braiding on both ends.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EC.

technical specification:
awg-no. 26
no.pairs x cross-sec. mm² 4 X 2 X 0,14
outer ø app. - mm 9,9
cop. weight - kg/km 45,0
weight app. - kg/km 140,0
helukabel part number 21067