*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Belden 1477A 18 AWG 12 Pair 22 AWG 1 Conductor Bare Copper 300V Instrumentation Cable
Description:-
UL Instrumentation, 12 Pair 18+22AWG (7x26+7x30) Bare Copper, PVC Insulation E1 Color Code, Individual and Overall Beldfoil Shield, Black PVC Outer Jacket, PLTC ITC CMG AWM 2464 SUN RES
Insulation:-
Element: Pair(s)
• Material: PVC - Polyvinyl Chloride
• Nom. Thickness: 0.017 in (0.43 mm)
• Nom. Insulation Diameter: 0.080 in (2.0 mm)
Element: Comm Wire(s)
• Material: PVC - Polyvinyl Chloride
• Nom. Thickness: 0.019 in (0.48 mm)
• Nom. Insulation Diameter: 0.066 in (1.7 mm)
Inner Shield:-
Element: Pair(s)
• Shield Type: Tape
• Material: Bi-Laminate (Alum+Poly)
• Coverage: 100%
• Drainwire Type: 20 AWG (7x28) TC - Tinned Copper
Element: Comm Wire(s)
• No Shield
Outer Shield:-
• Shield Type: Tape
• Material: Bi-Laminate (Alum+Poly)
• Coverage: 100%
• Drainwire Type: 18 AWG (7x26) TC - Tinned Copper
Outer Jacket:-
• Material: PVC - Polyvinyl Chloride
• Nom. Thickness: 0.063 in (1.6 mm)
• Nom. Diameter: 0.764 in (19.4 mm)
• Overall Cable Diameter (Nominal): 0.764 in (19.4 mm)
Standards:-
• Operating Temperature Range: -30°C to +105°C
• UL Voltage Rating: 300 V (PLTC, CMG, AWM 2464), 150 V (ITC)
Applications:-
• Industrial Control, Raceways, Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...), low voltage digital control (24v, …), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners
Specifications:-
• Size (AWG): 18
• No. of Pair: 12
• Stranding: 7x26
• Conductor Material: BC - Bare Copper
• Size (AWG): 22
• No. of Comm Wire: 1
• Stranding: 7x30
• Conductor Material: BC - Bare Copper
• Part Number: 1477A