The Medium Voltage Primary Underground Distribution (UD) cables consist of a Copper (filled or unfilled) conductor, covered with ethylene propylene rubber (EPR), a concentric neutral of helically applied copper wires, and a linear low-density polyethylene (LLDPE) jacket with 3 extruded red stripes.

Features:
• High dielectric strength
• Low moisture absorption
• Low dielectric loss
• Excellent resistance to treeing
• Jacket is sunlight-resistant
• Designed to operate continuously at a conductor temperature not exceeding
•105°C for normal operations
• 140°C for emergency overload
• 250°C for short circuit

Specifications:
Conductor Count: 1 conductor

Conductor: Fully annealed bare copper Class B compressed strand (filled or unfilled)

Gauge Sizes: 
• Filled: Available in 2 AWG through 1000 kcmil
• Unfilled: Available in 2 AWG through 1000 kcmil

Conductor Strand Shield: Extruded thermoset Super-Smooth semi-conducting polymer over the conductor

Insulation: Ethylene Propylene Rubber (EPR)

Insulation Shield: Extruded thermoset semi-conducting polymer over the insulation

Neutral: Helically applied, annealed, solid bare copper wires

Jacket: Linear Low-Density Polyethylene (LLDPE)

Jacket Marking: 00000 FT SUPERIOR ESSEX XXAWG (KCMIL) AL or CU 1/C XXKV XXX% INSUL LEVEL XXXMILS EPR AA X #BB LLDPE JKT MV-90 (UL) MADE IN USA MMDDYYYY

Packaging: Non-returnable wood reels in a variety of lengths and dimensions

Performance Compliances: 
•ASTM B-3
• ICEA S-94-649
• ICEA T-31-610 (water block compliance)
• AEIC CS8
• UL 1072 (MV-90)
• RUS U1

Applications:
• Suitable for underground primary power applications
• For wet or dry locations
• For direct burial or in duct

Note:
Also Available in:
• Copper Unfilled, 15kV 133% I.L., 175-mils
• Copper Filled, 15kV 133% I.L., 175-mils

technical specification
conductor size awg/kcmil
350
nominal conductor diameter¹ in (mm) 0.654 (16.6)
nominal insulation diameter¹ in (mm) 1.07 (27.1)
concentric neutral no. x awg 29 x 14
nominal jacket thickness¹ in (mm)
0.055 (1.40)
nominal overall diameter¹ in (mm) 1.39 (35.4)
nominal net weight¹ lbs/kft (kg/km) 2,008 (2,992)
ampacity (underground duct²) 437
ampacity (direct buried²) 498
superior essex cable part number E9HPT-A35B01CA00