Prysmian and Draka Cable 6 AWG Lifeline Power Cables RHW-2 or RW90 Two Hour Horizontal One-Hour Vertical Fire Resistive Cables in EMT G30065

Prysmian and Draka Cable 6 AWG Lifeline Power Cables RHW-2 or RW90 Two Hour Horizontal One-Hour Vertical Fire Resistive Cables in EMT G30065

Select gauge from drop-down menu for prices:

Prysmian and Draka Cable 6 AWG Lifeline Power Cables RHW-2 or RW90 Two Hour Horizontal One-Hour Vertical Fire Resistive Cables in EMT G30065
Prysmian and Draka Cable 6 AWG Lifeline Power Cables RHW-2 or RW90 Two Hour Horizontal One-Hour Vertical Fire Resistive Cables in EMT G30065

Conductors: Bare stranded copper, 8 AWG through 750kcmil

Insulation: High Temperature Mica Tapes layer, Ceramifiable silicone, Low Smoke Zero Halogen (LSZH)

Jacket: Cross-linked polyolefin (XLPO), Low Smoke Zero Halogen 

Identification: Lifeline® Power Cables are marked as follows: DRAKA MA P/N G[######] [X] [Y] LIFELINE c (UL) us E2268 RHW-2 OR RW90 600V FT4 ST1 VW1 FT1 (UL) R19359 FIRE-RESISTIVE CABLE FOR USE IN ELECTRIC CIRCUIT INTEGRITY SYSTEM FHIT.#25B AND SYSTEM FHIT.#25C (MONTH/YEAR) (SEQUENTIAL FOOTAGE)

Applications:
• Lifeline® fire resistive cables were designed to meet and have successfully passed the two hour fire rating certification test per UL 2196, Standard for Tests for Fire  Resistive Cables
• Lifeline® Cables can be used in the following applications to provide survivability during a fire:
- Fire Pumps
- Emergency Feeder Cables
- Ventilating Fans
- Exit Lighting
- Elevators
- Tall Buildings
- Hospitals
- Transit
- Oil Refineries
- Drilling Platforms
•Lifeline® Cables are preferred over Mineral Insulated (MI) cables, concrete encasement or the construction of fire rated assemblies based on the facts that Lifeline®  Cables are less costly, easier to install, and readily available.
•Fire resistive cables are required per NFPA 70, Articles 517, 695, 700, 708 and 760 as well as NFPA 72, NFPA 101, NFPA 130 and NFPA 502

Specifications and Ratings:
• Listed to UL 44, Thermoset Insulated Wires a nd Cables, as the following type: 
• RHW-2, 600 Volt, Rated 90oC Dry/90oC Wet 
• RW90, 600 Volt, Rated 90oC Dry/90oC Wet 
• Classified to UL 2196, Standard for Tests for Fire Resistive Cables, for two-hours in horizontal (H)  installations and one-hour in vertical (V) installations
• Electrical Circuit Integrity System (FHIT) No. 25B of the UL Fire Resistance Directory
• Sunlight Resistant
• FT4 Rated
• ST1 
• IEEE 1202
• NFPA 70, NFPA 101, NFPA 130, NFPA 502 compliant.

technical specification:
conductor size (awg /mcm) 6
number of strands 7
insulation thickness in (mm) 0.075 (1.9)
overall diameter in (mm) 0.37 (9.5)
approximate weight lbs./mft (kg/km) 129 (192)
ampacity1 90oc amps 75
Prysmian and Draka Cable Part Number G30065