Amercable Standard VFD 2 AWG Armored & Sheathed(TS) Power Cable Gexol Insulated Three Conductor 2kV Rated 110C 37-102-314

Amercable Standard VFD 2 AWG Armored & Sheathed(TS) Power Cable Gexol Insulated Three Conductor 2kV Rated 110C 37-102-314

Select gauge from drop-down menu for prices:

Amercable Standard VFD 2 AWG Armored & Sheathed(TS) Power Cable Gexol Insulated Three Conductor 2kV Rated 110C 37-102-314
Amercable Standard VFD 2 AWG Armored & Sheathed(TS) Power Cable Gexol Insulated Three Conductor 2kV Rated 110C 37-102-314

Power Conductors (x3): Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.

Ground Conductors (x3): Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11. Gexol® insulated and sized per UL 1277. Color: Green

Insulation (2kV): Gexol® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. Color: Gray with printed phase I.D. (Black-White-Red)

Shield: Overall tinned copper braid plus aluminum/polyester tape providing 100% coverage.

Jacket: A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL1309/CSA 245 and IEEE 1580.

Armor (Optional): Tinned copper basket weave wire armor per IEEE 1580 and UL 1309/CSA 245.

Sheath (Optional): A black, arctic grade, flame retardant, oil, abrasion, chemical and sunlight resistant thermosetting compound meeting UL 1309/CSA 245 and IEEE 1580.

Ratings & Approvals:
• 110°C Temperature Rating
• American Bureau of Shipping (ABS)
• Transport Canada
• Det Norske Veritas (DNV)
• Lloyd’s Register of Shipping (LRS)
• NVE: 95/1696, FAL
• UL Listed as Marine Shipboard Cable: (E111461)
• Unarmored Cable is UL Listed as Type TC (E123629)
• United States Coast Guard: November 2, 1987 / 9304

Application: A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications.

Features:
• Specially engineered cable design produces a longer cable life in VFD applications.
• Overall braid plus foil shield is engineered with 100% coverage and a surface transfer impedance <50 milliohms at 10MHz to contain EMI.
• Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive.
• High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
• Gexol’s lower dielectric constant (standard XLPEs, EPRs and other Type P insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system.
• 2kV insulation thickness is used to resist the potential 2-3x reflected voltages experienced in 600V VFD applications.
• Dual certified IEEE 1580 Type P and UL 1309/CSA 245 Type X110.
• Highest ampacity ratings: ABS 100°C, DNV 95°C, LRS 95°C, Transport Canada 95°C.
• Severe cold durability: exceeds CSA cold bend/cold impact (-40°C/-35°C).
• Flame retardant: IEC 332-3 Category A and IEEE 1202.
• Suitable for use in Class I, Division 1 and Zone 1 environments (armored and sheathed).
• Optional braid armor of bronze, aluminum or tinned copper.

technical specifications:
size awg/kcmil 2
mm2 34
nominal diameter inches* 1.392
weight lbs./1000 ft. 1512
dc resist. at 25°c ohms/1000 ft. 0.184
ac resist. at 90°c, 60 hz ohms/1000 ft. 0.244
inductive reactance ohms/1000 ft. 0.029
voltage drop at 90°c volts/amp/1000 ft. 0.368
grounding conductor** size (awg) 10
ampacity - 110°c 131
ampacity - 100°c 122
ampacity - 90°c 111
ampacity -75°c 93
amercable part number 37-102-314tsvfd