Conductor: Class B Compact concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM.
Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.
Insulation: Natural high dielectric strength EPROTENAX™ EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life.
Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.
Metallic Shield: Helically applied non-magnetic copper tape(s) over the insulation shield with a nominal overlap of 25%. A Mylar ribbon is longitudinally applied under the copper tape shield for phase identification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black.
Grounding Conductors: Bare stranded copper conductor per UL, ICEA, and ASTM.
Assembly: Phase identified conductors cabled with fillers and grounding conductors, forming a firm and cylindrical cable core. A binder tape is applied to maintain core symmetry and mechanical stability.
Mechanical Protection: High strength and high crush resistant Air Bag™ layer extruded over the core assembly.
Chemical Protection: A layer of Drylam™ which consists of aluminum tape and a chemical resistant extruded polymer layer is applied.
Jacket: Sunlight and moisture resistant polyvinyl chloride (PVC) jacket.
Installation:
• In Cable Tray
• Direct Buried
• Isolated in Air
• Dry Locations
With Messenger
• Conduit in Air
• Underground Duct
• Wet Locations
Industrial
Specifications and Ratings:
• ICEA- ICEA S-93-639/NEMA WC74
• UL 1072 Type MV-105, For CT USE Direct Buried Sunlight Resistant
• IEEE 383 & 1202 Flame Test
• CSA FT4 Flame Test CSA Cold Impact/Bend Test (-40C)
• MSHA Type MP and Type MP-GC
| technical specification: | |
| conductor | 2 awg cu |
| insulation thickness (mils) | 90 |
| ground wires no. | 3 |
| ground wires size | 10 awg |
| conductor diameter (in) (a) | 0.266 |
| insulation diameter (in) (b) | 0.49 |
| insulation shield diameter (in) (c) | 0.55 |
| overall jacket diameter (in) (d) | 1.64 |
| cable weight (lbs/kft) | 1855 |
| minimum bending radius (in) | 12 |
| ampacity (amps) ‡105°c in duct | 145 |
| ampacity (amps) ‡105°c in air/tray | 154 |
| impedance (micro-ohms/foot) pos/neg seq | 212 + j40 |
| impedance (micro-ohms/foot) zero seq. | 1223 + j24 |
| prysmian cable part number | QJ4580A |