TRAY CABLE - PLTC SHIELDED PAIRS WITH OVERALL SHIELD TYPE PLTC/ITC-ER - INSTRUMENTATION TRAY CABLE - 300 Volts - 105 Degrees C - 18 AWG - 12 Pairs

TRAY CABLE - PLTC SHIELDED PAIRS WITH OVERALL SHIELD TYPE PLTC/ITC-ER - INSTRUMENTATION TRAY CABLE - 300 Volts - 105 Degrees C - 18 AWG - 12 Pairs

Select gauge from drop-down menu for prices:

TRAY CABLE - PLTC SHIELDED PAIRS WITH OVERALL SHIELD TYPE PLTC/ITC-ER - INSTRUMENTATION TRAY CABLE - 300 Volts - 105 Degrees C - 18 AWG - 12 Pairs
TRAY CABLE - PLTC SHIELDED PAIRS WITH OVERALL SHIELD TYPE PLTC/ITC-ER - INSTRUMENTATION TRAY CABLE - 300 Volts - 105 Degrees C - 18 AWG - 12 Pairs
Technical Specifications:
Catalog Number 18012SPOS
AWG 18
No. of Pairs 12
OA Jkt. Thick. (MILS) 60
Appr. O.D. (IN) .718
Appr. Weight Lbs./ M Ft. 272
Stranding 7
PVC Insulation Thickness 15
Appr. O.D. (IN) .076

Specifications:

  • TRAY CABLE - PLTC SHIELDED PAIRS WITH OVERALL SHIELD
  • TYPE PLTC/ITC-ER - INSTRUMENTATION TRAY CABLE
  • Shielded Pairs with Overall Shield PVC Insulation with Overall PVC Jacket
  • 20 - 16 AWG • 300 Volts • 105°C

Description:
ADC’s Type PLTC/ITC-ER shielded pairs with an overall shield have PVC insulation with an overall sunlight resistant PVC jacket.

Application:
Class 1 Division 2 Industrial Hazardous Locations. For use in cable tray, raceway and conduit. For use with audio, intercom, control, energy management, and alarm circuits. For use where sunlight resistance is required.

Construction:

  • Conductors: Soft Drawn Annealed Bare Copper per ASTM B-3 and B-8. Concentric 7 strand. Tinned Copper available upon request.
  • Insulation PVC Thickness: Per UL 13 Table 7.3
  • Cabling: Pairs are cabled with staggered lays and wrapped with a foil free edge aluminum mylar tape. A stranded tinned copper drain wire is pulled in under each tape.
  • Overall Shield: Aluminum mylar tape providing 100% coverage with a flexible stranded tinned copper drain wire. Overall Jacket: A black, fame resistant, Polyvinyl Chloride (PVC) jacket is extruded over the assembly. The surface profle shall approximate that of the interior assembly. A rip cord shall be inserted under the jacket for ease of stripping.
  • Color Code: Method 1 - Black and White (White conductor in each pair printed alphanumerically for easy identifcation)

Industry Listings & Standards:

Black, Green, White, Red. Print on one side with a contrasting ink. An extruded stripe and other colors are available upon request.
  • UL Listed as PLTC/ITC per UL Standard 13 and 2250
  • Rated -25°C to 105°C
  • OSHA Acceptable
  • NEC Article 725
  • CSA FT4
  • IEEE1202 70,000 BTU Flame Test
  • ASTM - All Applicable Standards

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question