| Technical Specifications: | |
| Catalog Number/HWC Part # | HW290 10104 |
| Size AWG/kcmil | 1/0 |
|
Size (mm2) |
54 |
| Number of Conductors | 4 |
| Grounding Conductor AWG/kcmil | 6 |
| Nominal Diameter (inches) | 1.468 |
| Weight (lbs./1000 ft.) | 2107 |
| 90°C NEC Ampacity | 136 |
| 75°C NEC Ampacity | 120 |
| DC Resistance at 25°C(Ohms/1000 ft.) | 0.117 |
| AC Resistance at 90°C, 60 Hz (Ohms/1000 ft.) | 0.147 |
| Inductive Reactance (Ohms/1000 ft.) | 0.030 |
| Voltage Drop (Volts/Amp/1000 ft.) | 0.235 |
| HL Listed | -- |
Specifications:
- HW290
- HL Listed CIR® Power Cable
- Three & Four Conductor + Ground
- 0.6/1kV 90°C Gexol® Insulation
Application:
Designed and constructed to be a flexible alternative
to Type MC cable where crush and impact protection in
arctic conditions is required.
Conductors:
Soft annealed flexible stranded tinned copper per
IEEE 1580 Table 11.
Insulation:
Gexol cross-linked flame retardant polyolefin, meets
requirements for Type P of IEEE 1580 and Type X110 of UL
1309/CSA 245. 600V/IEC 1000V.
Grounding Conductor:
Soft annealed, flexible stranded, tinned copper sized in
accordance with UL 1277. 4 AWG and larger: uninsulated ground.
Jacket:
A black, flame retardant, oil, abrasion, chemical and sunlight
resistant thermoset compound meeting UL 1309/CSA 245 and
IEEE 1580.
Ratings & Approvals :
- 90°C temperature rating
- UL Listed as Marine Shipboard Cable (E111461)
- UL Listed as Type TC-ER
- UL Listed as Type TC-ER-HL*
- American Bureau of Shipping (ABS) (99-BT5905-X)
- Flame Retardant – IEEE 1202
- Suitable for use in Class I, Div 2 & Zone 2 environments
- Suitable for use in Class I, Div 1 & Zone 1 environments*
- *Cables up to 1” in OD
Features:
- Complies with the requirements for TC-ER-HL* per UL 2225
- Gas & vapor tight – impervious to water and air
- Smaller bend radius (up to 40% smaller) than Type MC
- Reduced tray fill (up to 35% less) compared to Type MC
- Considerably more flexible than Type MC
- Brittle point as per ASTM D 746-07 exceeds -65°C for
- Jacket and -75°C for Insulation
- Exceeds CSA cold bend / cold impact (-40°C / -35°C)
|
Power and Control Cable Color Legend: |
|
| Conductor # | Color |
| 1 | Black |
|
2 |
Red |
| 3 | Blue |
| 4 | Orange |