Belden 9418 Cable 18 AWG 4 Conductors Audio Control and Instrumentation Overall Beldfoil Shield Non Plenum Cable

Belden 9418 Cable 18 AWG 4 Conductors Audio Control and Instrumentation Overall Beldfoil Shield Non Plenum Cable

Regular price $3.96 $2.64 Sale /per Foot

Belden 9418 Cable 18 AWG 4 Conductors Audio Control and Instrumentation Overall Beldfoil Shield Non Plenum Cable

Description:
• 18 AWG stranded (19x30) tinned copper conductors, conductors cabled, semi-rigid PVC insulation, overall Beldfoil® shield (100% coverage), 20 AWG stranded tinned copper drain wire, PVC jacket.

Insulation:
• Material: S-R PVC - Semi-Rigid Polyvinyl Chloride
• Wall Thickness (mm): 0.2794

Outer Shield Drain Wire AWG:
• AWG: 20
• Stranding: Stranded
• Material: TC - Tinned Copper

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Wall Thickness (mm): 0.889

Overall Cabling Lay Length and Direction:
• Length (mm): 50.800
• Twists (twist/m): 19.686 (Left Hand Direction)

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -20°C To +80°C
• UL Temperature Rating: 80°C (UL AWM Style 2464)
• Bulk Cable Weight: 62.504 Kg/Km
• Max. Recommended Pulling Tension: 444.820 N
• Min. Bend Radius/Minor Axis: 63.500 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG
• NEC Articles: 800
• CEC/C(UL) Specification: CMG
• AWM Specification: UL Style 2464 (300 V 80°C)
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 04/01/2005
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Capacitance Conductor to Conductor (pF/m): 131.240
• Nom. Capacitance Cond. to Other Conductor & Shield (pF/m): 236.232
• Nom. Conductor DC Resistance @ 20°C (Ohm/km): 21.3265
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/km): 27.8885
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 5 Amps/Conductor @ 25°C ambient (10C Temp. Rise)

Flame Test:
• UL Flame Test: UL1685 UL Loading
• CSA Flame Test: FT4

Suitability:
• Suitability - Indoor: Yes

Plenum/Non-Plenum:
• Plenum (Y/N): No
• Plenum Number: 89418 or 82418

technical specification:
awg 18
# conductors 4
stranding 19x30
no. of conductors 4
conductor material tinned copper
outer shield - type tape
outer shield - material aluminum foil-polyester tape
overall cable- nominal dia. (mm) 6.223
belden cable part number 9418