Uses and Applications of EPR Hypalon 5000 Volts Unshielded Type MV 90 Power Cables

EPR Hypalon 5kv Unshielded Type MV 90 Power Cables are constructed using Class B stranded annealed uncoated copper conductors and ethylene propylene rubber (EPR) insulations. Conductors shall be covered with a layer of extruded conducting thermosetting compound. These cables are designed with a Hypalon jacket applied directly over the insulation surface.

SPECIFIC APPLICATIONSOF EPR HYPALON 5000 VOLTS UNSHIELDED TYPE MV 90 POWER CABLES

EPR Hypalon 5000 Volts Unshielded Type MV 90 Power Cable are specified for use at conductor temperatures not exceeding 90°C in wet or dry locations as per NEC. For other applications of these types of cables as non-shielded power cables at 5000 volts and 100% insulation level (grounded neutral) and 133% insulation level (ungrounded neutral), they should follow the below conditions:

1.Single conductors mounted on insulators in free air in indoor or outdoor locations. Circuit voltage ranges are 2400 volts, 4160 volts and 4800 volts.

2.Random lay singles in metal conduit and non-metallic conduit in dry locations at circuit voltage of 2400 volts.

3.160 volts and 4800 volts, and in damp or wet locations at circuit voltages of 2400 volts and 4160 volts.

4.Triplexed singles in metal conduit and non-metallic conduit in damp or wet location at circuit voltages of 4800 volts.

5.Single conductors or triplexed singles in cable tray, spaced block supports or in messenger supported rings in dry, damp or wet locations at circuit voltages of 2400 volts and 4160 volts.

6.Triplexed singles in cable tray, spaced block supports or in messenger supported rings in damp or wet locations at circuit voltage of 4800 volts.

7.Single conductors or triplexed singles, aerially, field-spun to grounded messenger in dry, damp or wet locations at circuit voltages of 2400 volts 4160 volts and 4800 volts.