Teck 90 Armoured Power Single Conductor 1000V XLPE/PVC/AIA/PVC - AWG Size Cond. 250

Teck 90 Armoured Power Single Conductor 1000V XLPE/PVC/AIA/PVC - AWG Size Cond. 250

TECK 90 ARMOURED POWER SINGLE CONDUCTOR 1000V XLPE/PVC/AIA/PVC - AWG SIZE COND. 250
Technical Specifications:
Catalog Number 05020-01-010
AWG Size Cond. 250
AWG Bond Wire
2
Insulation Thickness (in.) 0.090
Approximate Diameter (Over) Insul. (in.) 0.750
Approximate Diameter (Over) Inner Jacket (in.) 0.990
Approximate Diameter (Over) Armour (in.) 1.210
Approximate Diameter (Over) Outer Jacket (in.) 1.290
Copper Content LB/MFT 980
Copper Content KG/KM 1459
Net Weight w/ Armour LB/MFT
1490
Net Weight w/ Armour KG/ KM 2210
Amp. (30°C Ambient) 455

Specifications:

  • Teck 90 Armoured Power
  • Single Conductor 1000V
  • XLPE/PVC/AIA/PVC
  • CSA FT1 & FT4
  • CSA C22.2 No. 131 & 174
  • IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
  • ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test

CONSTRUCTION:

  • Conductor: Bare copper Class B compact or compressed stranded
  • Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
  • Ground (Bonding) Conductor: Concentric serving of solid bare copper wires applied over the insulation
  • Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
  • Armour: Aluminum Interlocked Armour (AIA)
  • Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), black
  • Options: Other coloured outer jacket and constructions available upon request

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.