HW109 Instrumentation Cable 600 Volt UL Type TC, 90°C Multiple Conductor Overall Shield FR-EP Insulation CPE Jacket Tinned Copper Conductor - 18 AWG - 3 Conductors
Select gauge from drop-down menu for prices:
- HW109 Instrumentation Cable 600 Volt UL Type TC, 90°C Multiple Conductor Overall Shield FR-EP Insulation CPE Jacket Tinned Copper Conductor
- HW109 Instrumentation Cable 600 Volt UL Type TC, 90°C Multiple Conductor Overall Shield FR-EP Insulation CPE Jacket Tinned Copper Conductor - 18 AWG - 2 Conductors
- HW109 Instrumentation Cable 600 Volt UL Type TC, 90°C Multiple Conductor Overall Shield FR-EP Insulation CPE Jacket Tinned Copper Conductor - 16 AWG - 2 Conductors
- HW109 Instrumentation Cable 600 Volt UL Type TC, 90°C Multiple Conductor Overall Shield FR-EP Insulation CPE Jacket Tinned Copper Conductor - 16 AWG - 3 Conductors
- HW109 Instrumentation Cable 600 Volt UL Type TC, 90°C Multiple Conductor Overall Shield FR-EP Insulation CPE Jacket Tinned Copper Conductor - 16 AWG - 4 Conductors
Technical Specifications: | |
Catalog Number | HW109 01803 |
Size AWG | 18 |
No. of Conductors |
3 |
Insulation Thickness Mils | 25 |
Jacket Thickness Mils | 45 |
Overall Diameter Inch |
0.31 |
Net Weight Lbs/Mft | 53 |
Specifications:
- HW109
- Instrumentation Cable
- 600 Volt UL Type TC, 90°C
- Multiple Conductor
- Overall Shield
- FR-EP Insulation
- CPE Jacket
- Tinned Copper Conductor
Application:
Superior flame-retardant cable for use in instrumentation and process control applications in caustic environments where protection from electrostatic interference is required. UL listed as Type TC and approved for installation indoors or outdoors, aerially, in conduits, ducts, cable trays and direct burial in circuits not exceeding 600 volts. May be installed at temperatures as low as -35°C and used in NEC Class 1, Division 2 hazardous locations. UL approved for NEC continuous operation at 90°C in wet and dry locations, 130°C for emergency overload conditions, and 250°C for short circuit conditions.
Conductors:
Tin-coated, soft annealed copper per ASTM B-33, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact).
Insulation:
Flame-retardant ethylene propylene rubber (FR-EP) per ICEA S-82-552.
Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.
Jacket:
Sunlight-resistant chlorinated polyethylene (CPE) per ICEA S-82-552 and UL Standard 1277. A ripcord is applied longitudinally under the jacket to facilitate stripping.
Flame Tests:
- IEEE 383 70,000 BTU/hr flame test
- IEEE 1202 70,000 BTU/hr
- UL 1277 70,000 BTU/hr flame test
- ICEA T-29-520 210,000 BTU/hr flame test
- CSA FT4 flame test
Color Code:
- ICEA Method 1, Table E-2
- ICEA Method 1, Table E-1 available upon request
Additional Standards:
- NEC Type per Articles 336, 392 and 501, and for Class 1 circuits per NEC Article 725
- NEMA WC-55