Belden 6059 14 and 8 AWG 600V TECK 90 Composite Armored Cable

Belden 6059 14 and 8 AWG 600V TECK 90 Composite Armored Cable

Belden 6059 14 and 8 AWG 600V TECK 90 Composite Armored Cable

Description:
• Composite 14 AWG stranded (7x22) and 8 AWG stranded (7x16) bare copper conductors, 10 AWG bare copper ground wire, .046x1A;(1.17mm) XLPE insulation, PVC inner jacket, aluminum interlocked armor, PVC outer jacket.

Ground Wire:
• Ground Wire (Y/N): Y
• Ground Wire AWG: 10
• Ground Wire Stranding: 7x18
• Conductor Material: BC - Bare Copper

Insulation:
• Material: XLPE - Cross Linked Polyethylene
• Wall Thickness (mm): 1.1684

Inner Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 17.78

Outer Jacket:
• Material: PVC - Polyvinyl Chloride
• Nom. Dia. (mm): 24.892

Armor:
• Armor Type: Interlocked
• Armor Material: Aluminum
• Diameter over Armor: 0.886

Mechanical Charactertistics (Overall):
• Operating Temperature Range: -40°C To +90°C
• Wet Temperature Range: -40°C To +90°C
• Dry Temperature Range: -40°C To +90°C
• Bulk Cable Weight: 904.826 Kg/Km
• Max. Recommended Pulling Tension: 5159.910 N
• Min. Bend Radius/Minor Axis: 248.920 mm

Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• CSA Specification: CSA C22.2#131; Hazardous Locations CSA C22.2#0.3 Clause 4.31 Low Acid Gas
• EU Directive 2011/65/EU (ROHS II): Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 01/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes

Electrical Characteristics (Overall):
• Nom. Conductor DC Resistance @ 20°C (Ohm/Km): 8.2025 (14 AWG)
• Nom. Conductor DC Resistance @ 20°C (Ohm/Km): 3.6091 (8 AWG)
• Max. Recommended Current: 12 Amps/Conductor @ 25°C (14 AWG)
• Max. Recommended Current: 44 Amps/Conductor @ 25°C (8 AWG)

Flame Test:
• CSA Flame Test: FT4

Suitability:
• Sunlight Resistance: Yes

Plenum/Non-Plenum:
• Plenum (Y/N): No

technical specification:
awg 14 and 8
# conductors 6
stranding 7x22 and 7x16
no. of conductors 6
conductor material bare copper
outer shield - material unshielded
overall cable- nominal dia. (mm) 24.917
belden cable part number 6059