Prysmian Cable 250 MCM AL 600 Volt USEI90 Low Voltage Utility Cables Q0ULSYC

Prysmian Cable 250 MCM AL 600 Volt USEI90 Low Voltage Utility Cables Q0ULSYC

Prysmian Cable 250 MCM AL 600 Volt USEI90 Low Voltage Utility Cables Q0ULSYC

Conductor: Multiple, Class B Compact, aluminum alloy 1350 per ASTM.

Insulation: High dielectric strength low temperature cross-linked polyethylene (XLPE) insulation, exhibiting an optimum balance of mechanical and electrical properties to assure extended cable life.

Jacket: Low-temperature appropriately colored polyvinyl chloride (PVC) jacket is extruded over each individual cable.

Assembly: Full or reduced neutral conductor, insulated and jacketed, class compact concentric strand aluminum alloy 1350 per ASTM, twisted together with the phase conductors.

Description: A twisted assembly, consisting of multiple aluminum phase conductors and one neutral conductor, each insulated with a low temperature, moisture resistant cross-linked polyethylene (XLPE) insulation that is formulated for a balance of flexibility and mechanical toughness, and a PVC jacket.

Options:
• Colored jacket
• Copper or ACM conductors
• Polyethylene-insulated USEI 75

Installation:
• Conduit in Air
• Direct Buried
• Underground Duct
• Wet Locations
• Dry Locations
• Utility Secondary
• Industrial

Specifications and Ratings:
• CSA- CSA C22.2 No. 52 -40oC
• FT1
• Sunlight Resistant
• For 90°C wet or dry operation.

technical specifications:
phase conductors 2-1/c 250 MCM al
neutral conductor 3/0 awg al
insulation thickness (mils) - phase 65
insulation thickness (mils) - neutral 55
jacket thickness (mils) - phase 65
jacket thickness (mils) - neutral 45
approximate diameter (mm) - phase (a) 20.32
approximate diameter (mm) - neutral (b) 16.15
approximate diameter (mm) - overall (c) 43.94
cable weight (kg/km) 1488
† ampacity (amps) 230
prysmian cable part number Q0ULSYC

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question