General Cable Power Cable Heavy Wall 1000MCM Single Conductor 600V VW-1 UL Type RHH/RHW-2 ULTROL® 60+

General Cable Power Cable Heavy Wall 1000MCM Single Conductor 600V VW-1 UL Type RHH/RHW-2 ULTROL® 60+

Select gauge from drop-down menu for prices:

General Cable Power Cable Heavy Wall 1000MCM Single Conductor 600V VW-1 UL Type RHH/RHW-2 ULTROL® 60+

Conductor: 14 AWG thru 1000 kcmil tinned annealed copper per ASTM B33; Class B stranding per ASTM B8

Insulation:
• Flame-retardant, heat-, moisture-, sunlightand radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE)
• Color Code: Black

Print:
• For 14 AWG thru 4/0 AWG: GENERAL CABLE (WC) ULTROL® 60+ 1/C XXAWG COPPER FR-XLPE (UL) TYPE RHH/RHW-2 600 V 90?C VW-1 NUCLEAR DAY MONTH YEAR Note: Sizes 1/0 AWG & larger include: SUN RES FOR CT USE, TRACEABILITY NUMBER & SEQUENTIAL FOOTAGE MARK
• For 250 kcmil thru 1000 kcmil: GENERAL CABLE (WC) ULTROL® 60+ 1/C XXXKCMIL COPPER FR-XLPE (UL) TYPE RHH/RHW-2 600 V 90?C SUN RES FOR CT USE VW-1 NUCLEAR DAY MONTH YEAR TRACEABILITY NUMBER SEQUENTIAL FOOTAGE MARK

Options: 
• Conductor stranding
• ISO Metric conductor
• Colored insulation

Applications:
• ULTROL® 60+ power cable is a 600 V heavy wall, insulated single conductor, thermoset, Class 1E rated wire construction specifically designed for applications in nuclear generating stations and where additional jacket protection is not required
• For use in Class 1E low-voltage power and lighting functions where optimum performance is required and where flame retardancy is critical
• May be installed in trays, conduit, ducts, or direct buried

Features: 
• Rated at 90?C wet or dry
• Fully traceable
• Qualified for 60-year service life
• Gamma and beta radiation resistant (up to 350 megarads)
• Submergence operability
• Long-term thermal endurance and superior electricals
• Excellent mechanical cut-through properties
• Long-term moisture and radiation stability
• Free stripping for ease of termination
• Meets cold bend test at -40°C

Industry Compliances: 
• Class 1E Qualified in accordance with IEEE 323-1974/2003 and IEEE 383-1974/2003
• ICEA S-95-658
• UL 44 RHH/RHW-2

Flame Test Compliances: 
• IEEE 383:1974
• IEEE 383:2003
• ICEA T-29-520
• IEEE 1202/FT4-1991, Aged & Unaged
• VW-1

Other: 
• Quality assurance program in accordance with NRC 10CFR50 Appendix B
• ANSI N45.2
• ASME NQA-1
• NIAC
• NUPIC

Packaging: Material to be shipped on non-returnable wooden reels

technical specifications:
cond. size (awg/kcmil) 1000
cond. strand 61/.1280
minimum avg. insulation thickness(inches) 0.110
minimum avg. insulation thickness(mm) 2.79
nominal cable o.d.(inches) 1.349
nominal cable o.d.(mm) 34.3
copper weight(lbs/1000 ft) 3088
copper weight(kg/km) 4595
net weight(lbs/1000 ft) 3392
net weight(kg/km) 5048
catalog number 15060.1000.1