General Cable Instrumentation Cable 16 Gauge 9 Triad 600V Individually Shielded Pairs or Triads Overall Shield VW-1 ULTROL® 60+

General Cable Instrumentation Cable 16 Gauge 9 Triad 600V Individually Shielded Pairs or Triads Overall Shield VW-1 ULTROL® 60+

Select gauge from drop-down menu for prices:

General Cable Instrumentation Cable 16 Gauge 9 Triad 600V Individually Shielded Pairs or Triads Overall Shield VW-1 ULTROL® 60+

Conductor: 18 AWG and 16 AWG tinned annealed copper per ASTM B33; Class B stranding per ASTM B8

Insulation: 
• Flame-retardant, heat-, moisture- and radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE) 
• Color code: Per ICEA Method 1 — Pairs: black and white; Triads: black, white and red. One conductor in each pair/triad is printed alpha-numerically for       easy identification 

Shields: 
• Individually shielded: pairs or triads are 100% shielded with a copper/polyester tape in contact with a stranded tinned copper drain wire and an overall             polyester electrical isolation tape 
• Overall shield: copper/polyester tape in contact with a stranded tinned copper drain wire 

Jacket: Flame-retardant, moisture-, oil-, sunlightand radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyolefin (XLPO) — Black 

Options: 
• Conductor stranding 
• ISO Metric conductors 
• Tinned copper braid shield 

Applications: 
• ULTROL® 60+ instrumentation cable is a 600 V individual shielded pairs or triads with overall shield, thermoset, Class 1E rated construction specifically       designed for applications in nuclear generating stations and where flame retardancy is critical 
• Designed for use on critical circuits where total isolation is required between pairs/ triads and from external interference  
• Can be installed in trays, conduit, ducts, or in direct burial applications 

Features: 
• Rated at 90?C wet or dry 
• Fully traceable 
• Qualified for 60-year service life 
• Gamma and beta radiation resistant (up to 350 megarads) 
• Submergence operability 
• Long-term thermal endurance and superior electricals 
• Excellent mechanical cut-through properties 
• Long-term moisture and radiation stability 
• Free stripping for ease of termination 
• Meets cold bend test at -40°C 

Industry Compliances: 
• Class 1E Qualified in accordance with IEEE 323-1974/2003 and IEEE 383-1974/2003 
• ICEA S-73-532 

Flame Test Compliances: 
• IEEE 383:1974 
• IEEE 383:2003 
• ICEA T-29-520
• IEEE 1202/FT4-1991, Aged & Unaged 
• VW-1 

Other: 
• Quality assurance program in accordance with NRC 10CFR50 Appendix B 
• ANSI N45.2 
• ASME NQA-1 
• NIAC 
• NUPIC 

Packaging: Material to be shipped on non-returnable wooden reels

technical specifications:
cond.size(awg) 16
no. of pairs/triads 9 STS
cond.strand 7/.0192
minimum avg.insulation thickness(inches) 0.025
minimum avg.insulation thickness(mm) 0.64
drain wire size(awg) 18
minimum avg.jacket thickness(inches) 0.080
minimum avg.jacket thickness(mm) 2.03
nominal cable o.d.(inches) 0.939
nominal cable o.d.(mm) 23.9
copper weight(lbs/1000 ft) 272
copper weight(kg/km) 405
net weight(lbs/1000 ft) 762
net weight(kg/km) 1134
catalognumber 25060.16.9T

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question