GENERAL CABLE Control Cable 12/9 Gauge Multi-Conductor 600V Overall Shield VW-1 UL Type TC-ER* ULTROL 60®+

GENERAL CABLE Control Cable 12/9 Gauge Multi-Conductor 600V Overall Shield VW-1 UL Type TC-ER* ULTROL 60®+

Select gauge from drop-down menu for prices:

GENERAL CABLE Control Cable 12/9 Gauge Multi-Conductor 600V Overall Shield VW-1 UL Type TC-ER* ULTROL 60®+

Product Details

Conductor: 14 AWG thru 10 AWG, tinned annealed copper; Class B stranding; 2 thru 37 conductors

Insulation:
• Flame-retardant , heat-, moisture- and radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE)
• Color code: per ICEA Method 1, Table E-1

Overall Shield: Copper/polyester tape in contact with a stranded tinned copper drain wire

Jacket: Flame-retardant, moisture-, oil-, sunlightand radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyolefin (XLPO) —Black

Print: GENERAL CABLE (WC) ULTROL® 60+ XX/C XXAWG COPPER FR-XLPE XLPO SHIELDED 600 V 90°C SUN RES OIL RES I & II DIR BUR (UL) TYPE TC-ER* XHHW-2 VW-1 NUCLEAR DAY MONTH YEAR TRACEABILITY NUMBER SEQUENTIAL FOOTAGE MARK * -ER for > 2 conductors

Options:
 • Conductor stranding
 • ISO Metric conductors
 • E-2 color code
 • Longitudinal corrugated tinned copper tape shield

Applications:
• ULTROL® 60+ control cable is a 600 V overall shielded, multi-conductor, thermoset, Class 1E rated construction specifically designed for applications in nuclear generating stations and where flame retardancy is critical
• Where optimum performance is required for use on Class 1E circuits when shielding from external electrostatic interference is required
• Can be installed in trays, conduit, ducts, or in direct burial applications

Features:
• Rated at 90˚C wet or dry
• Fully traceable
• Qualified for 60-year service life
• Gamma and beta radiation resistant (up to 350 megarads)
• Submergence operability
• Long-term thermal endurance and superior electricals
• Excellent mechanical cut-through properties
• Long-term moisture and radiation stability
• Free stripping for ease of termination
• Meets cold bend test at -40°C

Industry Compliances:
• Class 1E Qualified in accordance with IEEE 323-1974/2003 and IEEE 383-1974/2003
• ICEA S-73-532
• UL 1277 Type TC-ER*
• UL 44 XHHW-2 * -ER for > 2 conductors

Flame Test Compliances:
• IEEE 383:1974
• IEEE 383:2003
• ICEA T-29-520
• IEEE 1202/FT4-1991, Aged & Unaged
• VW-1

Other:
• Quality assurance program in accordance with NRC 10CFR50 Appendix B
• ANSI N45.2
• ASME NQA-1
• NIAC
• NUPIC

Packaging: Material to be shipped on non-returnable wooden reels

technical specifications:
cond. size (awg) 12
no. of cond. 9
cond. strand 7/.0305
minimum avg. insulation thickness (inches) 0.030
minimum avg. insulation thickness (mm) 0.76
drain wire size (awg) 14
minimum avg. jacket thickness (inches) 0.060
minimum avg. jacket thickness(mm)
1.52
nominal cableo.d.(inches) 0.745
nominal cableo.d.(mm) 18.9
copper weight (lbs/1000 ft) 197
copper weight (kg/km) 293
net weight (lbs/1000 ft) 394
net weight (kg/km) 587
catalog number 30060.12.9

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question