Product Information
| Technical Specifications: | |
| Catalog Number | 19001-16-060 |
| AWG Size Cond. | 600 |
|
AWG Bond Wire |
1/0 |
| Insulation Thickness (in.) | 0.090 |
| Approximate Diameter (Over) Insul. (in.) | 1.055 |
| Approximate Diameter (Over) Inner Jacket (in.) | 1.355 |
| Approximate Diameter (Over) Armour (in.) | 1.595 |
| Approximate Diameter (Over) Outer Jacket (in.) | 1.705 |
| Copper Content LB/MFT | 2174 |
| Copper Content KG/KM | 3235 |
|
Net Weight w/ Armour LB/MFT |
2929 |
| Net Weight w/ Armour KG/ KM | 4359 |
| Amp. (30°C Ambient) | 780 |
Specifications:
- Teck 90 Armoured Power
- Unshielded Single Conductor
- 90 MIL 100%/133% 5kV
- XLPE/PVC/AIA/PVC
- CSA FT1 & FT4
- CSA C22.2 No. 131 & 174
- IEEE 383 & 1202 (70,000 BTU/hr) Flame Test
- ICEA T-30-520 (70,000 BTU/hr) Vertical Flame Test
CONSTRUCTION:
- Conductor: Bare copper Class B compact or compressed stranded
- Conductor Shield: Extruded thermoset semi-conducting shield
- Insulation: Cross-Linked Polyethylene (XLPE) Type RW90
- Ground (Bonding) Conductor: Concentric serving of solid bare copper wires applied over the insulation
- Inner Jacket: Flame-retardant and moisture resistant Polyvinyl Chloride (PVC)
- Armour: Aluminum Interlocked Armour (AIA)
- Outer Jacket: Low-temperature, moisture and sunlight resistant Polyvinyl Chloride (PVC), orange
- Options: Other coloured outer jacket and constructions available upon request