*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Description:
• 24 pair, 16 AWG, Stranded (7x24) Tinned Copper, 600V, Individually Foil Shielded Pairs, Overall Beldfoil Sheild, Tinned Copper Drain Wires, XLP Insulation, Sunlight- and oil-resistant TPE jacket.
Insulation:
• Material: XLP - Cross-Linked Polyolefin
Inner Shield:
• Type: Tape
• Inner Shield Material: Aluminum Foil-Polyester Tape
Inner Shield Drain Wire AWG:
• AWG: 18
• Stranding: 7x26
• Conductor Material: TC - Tinned Copper
Outer Shield Drain Wire AWG:
• AWG: 16
• Stranding: 7x24
• Conductor Material: TC - Tinned Copper
Outer Jacket:
• Material: TPE - Thermoplastic Elastomer
• Outer Jacket Ripcord: Yes
Mechanical Characteristics (Overall):
• Operating Temperature Range: -25°C Cold Impact, -40°C To +90°C, -55°C Cold Bend
• UL Temperature Rating: 90°C Wet/Dry
• Installation Temperature Rating: -25°C
• Bulk Cable Weight: 1219 lbs/1000 ft.
• Max. Recommended Pulling Tension: 2286 lbs.
• Min. Bend Radius/Minor Axis: 16.500 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: TC-ER
• CSA Specification: AWM I A/B II A/B, C22.2 #230 Type TC; C22.2#239 Type CIC
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
• Other Specification: IEC 61158-2 (ISA/SP-50) Type A
Electrical Characteristics (Overall):
• Unaveraged Impedance (Ohm): 100
• Nom. Inductance (μH/ft): 0.220
• Nom. Capacitance Conductor to Conductor (pF/ft): 22.000
• Maximum Capacitance Unbalance (pF/ft): 1.2
• Nominal Velocity of Propagation: VP (%): 64.000
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 4.200
• Max. Operating Voltage - UL: 600 V RMS
• Max. Operating Voltage - Other: 600V RMS (CSA CIC type TC)
• Max. Recommended Current: 7.2 Amps/Conductor
Flame Test:
• UL Flame Test: UL1581 Vertical Tray
• CSA Flame Test: FT4
• IEC Flame Test: 60332-3-24 (Category C)
Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
• Sunlight Resistance: Yes
• Oil Resistance: Yes
Plenum/Non-Plenum:
• Plenum(Y/N): No
| technical specification: | |
| awg | 16 |
| # pairs | 24 |
| stranding | 7x24 |
| no. of conductors | 48 |
| conductor material | tinned copper |
| diameter (in.) | - |
| outer shield - type | tape |
| outer shield - material | aluminum foil-polyester tape |
| overall cable - nominal diameter (in.) | 1.638 |
| belden cable part number | 2134A |