Description:
• 2 pair, 16 AWG stranded (7x24) tinned copper conductors, polyolefin insulation, individual and overall Beldfoil® shield (100% coverage), tinned copper drain wire, oil-resistant PVC jacket.
Insulation:
• Material: PO - Polyolefin
Inner Shield:
• Type: Tape
• Inner Shield Material: Aluminum Foil-Polyester
Inner Shield Drain Wire AWG:
• AWG: 20
Outer Shield Drain Wire AWG:
• AWG: 16
• Stranding: 7x24
• Conductor Material: TC - Tinned Copper
Outer Jacket:
• Material: PVC - Polyvinyl Chloride
Mechanical Characteristics (Overall):
• Operating Temperature Range: -40°C To +105°C
• UL Temperature Rating: 105°C
• Bulk Cable Weight: 130 lbs/1000 ft.
• Max. Recommended Pulling Tension: 143 lbs.
• Min. Bend Radius/Minor Axis: 5.800 in.
Applicable Specifications and Agency Compliance (Overall):
Applicable Standards and Environmental Programs:
• NEC/(UL) Specification: CMG, CMX-Outdoor, ITC, PLTC-ER
• CEC/C(UL) Specification: CMG
• EU Directive 2011/65/EU (ROHS II): Yes
• EU CE Mark: Yes
• EU Directive 2000/53/EC (ELV): Yes
• EU Directive 2002/95/EC (RoHS): Yes
• EU RoHS Compliance Date (mm/dd/yyyy): 09/01/2006
• EU Directive 2002/96/EC (WEEE): Yes
• EU Directive 2003/11/EC (BFR): Yes
• CA Prop 65 (CJ for Wire and Cable): Yes
• MII Order #39 (China RoHS): Yes
Electrical Characteristics (Overall):
• Unaveraged Impedance (Ohm): 100
• Nom. Inductance (μH/ft): 0.19
• Nom. Capacitance Conductor to Shield (pF/ft): 45.0
• Nom. Mutual Capacitance (pF/ft): 24.0
• Maximum Capacitance Unbalance (pF/ft): 1.2
• Nominal Velocity of Propagation: VP (%): 66
• Nom. Conductor DC Resistance @ 20°C (Ohm/1000 ft): 4.200
• Nominal Outer Shield DC Resistance @ 20°C (Ohm/1000 ft): 4.9
• Ind. Pair Nominal Shield DC Resistance @ 20 Deg. C: 7.500 Ohm/1000 ft
• Max. Operating Voltage - UL: 300 V RMS
• Max. Recommended Current: 5.2 Amps/Conductor
Flame Test:
• UL Flame Test: UL1685 FT4 Loading
• IEC Flame Test: 60332-3-24 (Category C)
• IEEE Flame Test: 1202
Suitability:
• Suitability - Indoor: Yes
• Suitability - Outdoor: Yes
• Sunlight Resistance: Yes
Plenum/Non-Plenum:
• Plenum(Y/N): No
| technical specification: | |
| awg | 16 |
| # pairs | 2 |
| stranding | 7x24 |
| no. of conductors | 4 |
| conductor material | tinned copper |
| diameter (in.) | 0.059 |
| outer shield - type | tape |
| outer shield - material | aluminum foil-polyester tape |
| overall cable - nominal diameter (in.) | 0.580 |
| belden cable part number | 1361A |