• Power Cable Heavy Wall Single Conductor 600V VW-1 UL Type RHH/RHW-2 ULTROL 60+

    Product Details

    The heavy wall power cable is made of tinned annealed copper material and falls under class B stranding as described by ASTM B8. The cable can perform well in areas that exhibit adverse environmental conditions like heat, extreme cold, or radiation. It is used in nuclear generating plants and other industries where power distributions and controls are exposed to heat, radiations, and other effects. The insulation offers more protection for durability and extended use as well as workability.

    Applications :
    • ULTROL® 60+ power cable is a 600 V heavy wall, insulated single conductor, thermoset, Class 1E rated wire construction specifically designed for applications in nuclear generating stations and where additional jacket protection is not required
    • For use in Class 1E low-voltage power and lighting functions where optimum performance is required and where flame retardancy is critical May be installed in trays, conduit, ducts, or direct buried
    • This wire works well in application where flame retardancy is needed. It is designed to work in areas where there may be no need for jacket protection but where great performance is required. The cable is used in nuclear generation facilities, petrochemical refineries, steel mills, mining, wastewater treatment plants, and in chemical plants. These are areas that suffer more heat or extreme low temperatures meaning the wires should be able to withstand those elements. Among the different installations where the cable may be used are such as in conduits, trays, underground duct, and in applications requiring direct burial.

    Insulation :
    • Flame-retardant, heat-, moisture-, sunlight and radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE)
    • Color Code: Black
    • While this cable does not have a jacket, it is insulated using a cross-linked polyethylene material. The insulation is specially treated to form a thermoset material, which is highly resistant to moisture, heat, flame or fire, radiation, and sunlight.

    cond.
    size
    (awg/
    kcmil)
    cond.
    strand
    minimum avg.
    insulation
    thickness
    nominal
    cable
    o.d.
    copper weight net weight general cable
    part number
    inches mm inches mm lbs/
    1000 ft
    kg/
    km
    lbs/
    1000 ft
    kg/
    km
    14 7/.0242 0.045 1.14 0.163 4.14 13 19 23 35 15060.14.1
    12 7/.0305 0.045 1.14 0.182 4.62 20 30 34 51 15060.12.1
    10 7/.0385 0.045 1.14 0.205 5.21 32 48 48 72 15060.10.1
    8 7/.0486 0.060 1.52 0.266 6.76 51 76 78 116 15060.8.1
    6 7/.0612 0.060 1.52 0.303 7.70 81 121 114 169 15060.6.1
    4 7/.0772 0.060 1.52 0.350 8.89 129 192 169 251 15060.4.1
    2 7/.0974 0.060 1.52 0.409 10.4 205 305 254 378 15060.2.1
    1 19/.0664 0.080 2.03 0.488 12.4 258 384 329 490 15060.1.1
    1/0 19/.0745 0.080 2.03 0.527 13.4 326 485 404 601 15060.1/0.1
    2/0 19/.0837 0.080 2.03 0.572 14.5 411 612 498 742 15060.2/0.1
    3/0 19/.0940 0.080 2.03 0.622 15.8 518 771 615 915 15060.3/0.1
    4/0 19/.1055 0.080 2.03 0.678 17.2 653 972 761 1133 15060.4/0.1
    250 37/.0822 0.095 2.41 0.754 19.2 772 1149 908 1352 15060.250.1
    350 37/.0973 0.095 2.41 0.857 21.8 1081 1609 1241 1846 15060.350.1
    500 37/.1162 0.095 2.41 0.986 25.0 1544 2297 1734 2580 15060.500.1
    750 61/.1109 0.110 2.79 1.199 30.5 2316 3446 2581 3840 15060.750.1
    1000 61/.1280 0.110 2.79 1.349 34.3 3088 4595 3392 5048 15060.1000.1

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours

    Captcha Image

    This product has no related products.

    NOW VIEWING

    Power Cable Heavy Wall Single Conductor 600V VW-1 UL Type RHH/RHW-2 ULTROL 60+

    Request a Quote

Request a Quote

Receive A Response In 5 Minutes Or Less During Business Hours

Sign up for our newsletter

Register with Nassau today.

Subscribe to Newsletter