General Cable Power Cable Dual Wall 350MCM Single Conductor 600V VW-1 UL Type RHH RHW-2 ULTROL® 60+

General Cable Power Cable Dual Wall 350MCM Single Conductor 600V VW-1 UL Type RHH RHW-2 ULTROL® 60+

Select gauge from drop-down menu for prices:

General Cable Power Cable Dual Wall 350MCM Single Conductor 600V VW-1 UL Type RHH RHW-2 ULTROL® 60+

Conductor: 14 AWG thru 1000 kcmil tinned annealed copper per ASTM B33; Class B stranding per ASTM B8

Insulation: 
• Flame-retardant, heat-, moisture- and radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyethylene (FR-XLPE)
• Color Code: White

Jacket: Flame-retardant, moisture-, oil-, sunlightand radiation-resistant, thermoset ULTROL® 60+ Cross-linked Polyolefin (XLPO) — Black

Options:
• Conductor stranding
• ISO Metric conductor

Applications:
• ULTROL® 60+ power cable is a 600 V dual wall, insulated single conductor, thermoset, Class 1E rated wire construction specifically designed for applications in nuclear generating stations and where additional jacket protection is required
• For use in Class 1E low-voltage power and lighting functions where optimum performance is required and where flame retardancy is critical
• May be installed in trays, conduit, ducts, or direct buried

Features: 
• Rated at 90?C wet or dry
• Fully traceable
• Qualified for 60-year service life
• Gamma and beta radiation resistant (up to 350 megarads)
• Submergence operability
• Long-term thermal endurance and superior electricals
• Excellent mechanical cut-through properties
• Long-term moisture and radiation stability
• Free stripping for ease of termination
• Meets cold bend test at -40°C

Industry Compliances:
• Class 1E Qualified in accordance with IEEE 323-1974/2003 and IEEE 383-1974/2003
• ICEA S-95-658
• UL 44 RHH/RHW-2

Flame Test Compliances:
• IEEE 383:1974
• IEEE 383:2003
• ICEA T-29-520
• IEEE 1202/FT4-1991, Aged & Unaged
• VW-1

Other:
• Quality assurance program in accordance with NRC 10CFR50 Appendix B
• ANSI N45.2
• ASME NQA-1
• NIAC
• NUPIC

Packaging: Material to be shipped on non-returnable wooden reels

technical specification:
cond. size (awg/kcmil) 350
cond. strand 37/.0973
minimum avg. insulation thickness(inches) 0.065
minimum avg. insulation thickness(mm) 1.65
minimum avg. jacket thickness(inches) 0.065
minimum avg. jacket thickness(mm) 1.65
nominal cable o.d.(inches) 0.932
nominal cable o.d.(mm) 23.7
copper weight(lbs/1000 ft) 1081
copper weight(kg/km) 1609
net weight(lbs/1000 ft) 1302
net weight(kg/km) 1937
catalog number 17560.350.1

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question