    Conductor:
    • Tinned flexible circular copper, 0.75, 1.0 & 1.5 sqmm (BS6360 class 5)
    • Tinned stranded circular copper, 2.5 sqmm (BS 6360, class 2)

    Insulation: EP-rubber, GP4 to BS 7655: section 1.2

    Pair/Triple/Quad twisting / lay up:
    • Colour coded cores twisted together to form a pair, triple or quad, which is individually screened with aluminium backed polyester tape with a tinned copper drain wire. Each pair, triple or quad is wrapped with polyester tape to prevent electrical contact with adjacent pairs, triples or quads.
    • Individually shielded pairs, triples or quads are laid up in concentric layers and wrapped with a PETP tape.
    • Pairs, triples, or quads are identified by numbers printed directly on the insulated conducors.

    Inner Covering: Flame retardant and halogen-free thermoset compound

    Tape Over Inner Covering: PET tape + rubberized Polyamide tape

    Armour/Screen: Galvanized steel wire braid

    Tape Over Armour / Screen: PET tape  + rubberised Polyamide tape

    Outer Sheath: Flame retardant, halogen-free, enhanced oil-resisting thermoset compound (LSF), SW4 to BS 7655 section 2.6

    Marking Text: "metre mark" "year" "DRAKA" "RFCU(I)" "UKOOA code" "150/250V" "number of pair, triples or quads" "conductor size" "BS6883" "IEC60332-3-22" (marking may differ on cable actually supplied)

    Outer Sheath Colour: Grey or Blue

    Core Identification:
    • Pair - Black-White, numbered 1-1, 2-2, 3-3....
    • Triple - Black-White-Red, numbered 1-1-1, 2-2-2, 3-3-3 ....
    • Quad - Black-White-Red-Blue, numbered 1-1-1-1, 2-2-2-2....
    • Each core is identified by contrasting numerals & words repeated along the whole length of the cable.

    Operating Temperature: 90°C

    Operating Voltage: 250V

    Standards applied:
    • BS6883 / UKOOA - Design
    • BS6360 class 2 or 5 - Conductor
    • BS7655 section 1.2 - Insulation
    • BS7655 section 2.6 - Sheath
    • IEC 60332-1 - Flame Retardant
    • IEC60332-3-22 - Flame retardant
    • IEC60754-1.2 - Halogen Free
    • IEC 61034-1.2 - Low Smoke

    Description:
    • RFCU(I) 250V 1PAIR 0.75mm2
    • RFCU(I) 250V 1PAIR 0.75mm2
    • RFCU(I) 250V 3PAIR 0.75mm2
    • RFCU(I) 250V 3PAIR 0.75mm2
    • RFCU(I) 250V 7PAIR 0.75mm2
    • RFCU(I) 250V 7PAIR 0.75mm2
    • RFCU(I) 250V 12PAIR 0.75mm2
    • RFCU(I) 250V 12PAIR 0.75mm2
    • RFCU(I) 250V 19PAIR 0.75mm2
    • RFCU(I) 250V 1PAIR 1mm2
    • RFCU(I) 250V 1PAIR 1mm2
    • RFCU(I) 250V 3PAIR 1mm2
    • RFCU(I) 250V 1PAIR 1.5mm2
    • RFCU(I) 250V 3PAIR 1.5mm2
    • RFCU(I) 250V 3PAIR 1.5mm2
    • RFCU(I) 250V 20PAIR 1.5mm2
    • RFCU(I) 250V 1TRIP 0.75mm2
    • RFCU(I) 250V 3TRIP 0.75mm2
    • RFCU(I) 250V 3TRIP 0.75mm2
    • RFCU(I) 250V 7TRIP 0.75mm2
    • RFCU(I) 250V 7TRIP 0.75mm2
    • RFCU(I) 250V 12TRIP 0.75mm2
    • RFCU(I) 250V 12TRIP 0.75mm2
    • RFCU(I) 250V 1TRIP 1mm2
    • RFCU(I) 250V 1TRIP 1.5mm2
    • RFCU(I) 250V 1TRIP 1.5mm2
    • RFCU(I) 250V 1QUAD 0.75mm2
    • RFCU(I) 250V 1QUAD 0.75mm2
    • RFCU(I) 250V 1QUAD 1mm2
    • RFCU(I) 250V 1QUAD 1mm2
    • RFCU(I) 250V 1QUAD 1.5mm2

    Sheath Colour:
    • GREY
    • BLUE

    Design Standard:
    • BS 6883 : 1999
    • BS 6883 : 1991

    Application:
    • Fixed installation for instrumentation, communication, control and alarm systems in both EX- and safe areas.
    • Enhanced MUD resistant version also available for use in areas exposed to mud and drilling / cleaning fluids, meeting the mud resistance requirement in NEK 606.

    Range and Dimensions
    no. of
    cores in
    element
    number
    of
    elements
    cross-
    section
    core,
    mm2
    cond.
    dia.,
    mm
    ins.
    thck.,
    mm
    thck.
    inner
    sheath,
    mm
    dia.
    inner
    sheath,
    mm
    dia.
    braid
    wire,
    mm
    thck.
    outer
    sheath,
    mm
    approx.
    overall
    dia.,
    mm
    weight
    of cable
    approx.
    (kg/km)
    copper
    content
    approx.
    (kg/km)
    ukooa
    code
    prysmian
    and
    draka cable
    part number
    2 1 0.75 1.15 0.8 1 7.5 0.3 1.2 11.5 230 18 kkf00 840001
    2 3 0.75 1.15 0.8 1.2 12 0.3 1.4 16.5 430 53 kkh00 840226
    2 7 0.75 1.15 0.8 1.4 16.5 0.3 1.6 21 720 124 kkj00 840214
    2 12 0.75 1.15 0.8 1.6 22 0.3 1.8 27 1110 212 kkk00 840216
    2 19 0.75 1.15 0.8 1.8 26 0.45 2 32 1660 336 - 840238
    3 1 0.75 1.15 0.8 1 8 0.3 1.2 12 245 25 kkr00 840335
    3 3 0.75 1.15 0.8 1.3 14 0.3 1.5 18.5 530 73 kks00 840276
    3 7 0.75 1.15 0.8 1.5 18.5 0.3 1.7 23.5 900 170 kkt00 840272
    3 12 0.75 1.15 0.8 1.7 25 0.45 2 31 1530 293 kku00 840239
    4 1 0.75 1.15 0.8 1.2 9 0.3 1.3 13.5 310 31 kkx00 840002
    2 1 1 1.3 0.8 1 8 0.3 1.2 12 240 24 kkf01 840094
    2 3 1 1.3 0.8 1.3 13 0.3 1.4 17 490 71 kkh01 840100
    3 1 1 1.3 0.8 1.1 8.5 0.3 1.2 12.5 285 32 kkr01 840121
    4 1 1 1.3 0.8 1.2 9.5 0.3 1.4 14 340 41 kkx01 840336
    2 1 1.5 1.6 0.8 1.1 8.5 0.3 1.2 12.5 290 32 kkf02 840293
    2 3 1.5 1.6 0.8 1.3 14 0.3 1.5 18.5 560 95 kkh02 840275
    2 20 1.5 1.6 0.8 2 31.5 0.45 23 36 2430 635 kkl02 840235
    3 1 1.5 1.6 0.8 1.1 9 0.3 1.2 13 320 45 kkr02 840296
    4 1 1.5 1.6 0.8 1.2 10 0.3 1.4 14.5 370 57 kkx02 840337

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours

    Captcha Image

    This product has no related products.

    NOW VIEWING

    Prysmian and Draka Cable RFCU(i) 250V Instrumentation Individual Screened Flame Retardant, Halogen free Cable with oil resistance

    Request a Quote

Request a Quote

Receive A Response In 5 Minutes Or Less During Business Hours

Sign up for our newsletter

Register with Nassau today.

Subscribe to Newsletter