• Draka Cable Bostrig Type P VFD Power 2000V Shielded Three Conductor Unarmored or Armored and Sheathed Cable

    Product Details

    Conductors: Soft annealed stranded tinned copper per ASTM B 33. A polyester tape separator is used over the conductor.

    Insulation: Bostrig Type P chemically cross-linked polyolefin (XLPO), meeting IEEE 1580 (2001).

    Ground Conductors: All Bostrig Type P-VFD Cables listed in this specification sheet are built using system grounds equal to the aggregate cross-section of a phase conductor and can be in contact withor isolated from the overall shield. A system ground is REQUIRED for supplying power from the switchboard to the inverter and then to the motor. If the VFD cable is only being used between the motor and the inverter, a cable with a lesser ground can be utilized.

    Shield: Braided tinned copperand aluminum polyester tape for 100% coverage

    Jacket: Flame-retardant Arctic Neoprene, complying with Type N Neoprene as required in IEEE-1580. Thickness as shown in tables on opposite page.

    Armor (optional): Braided bronze in accordance with IEEE 1580.

    Sheath: Flame-retardant Arctic Neoprene applied over the armor, complying with Type N Neoprene as required in IEEE 1580. Thickness as shown in tables on opposite page.

    Applications:
    • Bostrig™ Type P shielded three conductor VFD Marine and Offshore Cable is designed specifically for use with variable frequency AC motor drives. This cable is designed to significantly mitigate the deleterious effects of high frequency harmonics and electromagnetic interference (EMI) on the motor /drive system as well as the adjacent environment.
    • Bostrig™ VFD cables have excellent resistance to oil, abrasion, moisture, vibration, sunlight, and ester based muds (Type P- MR). They are suitable for use in Class 1, Division 1 offshore applications (armored and sheathed) and complies with UL 1277 Type TC-ER extended runs requirements.
    • The standard insulation has a continuous operating temperature of 125°C, allowing for higher ampacity levels. These cables also meet cold bend requirements of -40°C and cold impact of -35°C (CSA 22.2 N0. 0.3).
    • This product may be manufactured in an unarmored or armored and sheathed version.

    Approvals:
    • IEEE 1580 and IEEE 45- Marine Shipboard Cable
    • UL 1309- Marine Shipboard Cable Type X110
    • CSA 22.2 No. 245- Marine Shipboard Cable Type X110
    • Det Norske Veritas (DNV)
    • American Bureau of Shipping (ABS)
    • Transport Canada Approved AMS400-20-2
    • Transport Canada 8700-20-2
    • Lloyd’s Register of Shipping (LRS)
    • United States Coast Guard-46CFR

    Features/Ratings:
    • Special ester-based mud resistant jacket also provides superior resistance to oil, abrasion, moisture, sunlight, crush and impact
    • High strand count conductors provide superior flexibility
    • Higher allowable conductor operating temperature results in increased ampacity
    • Hold bend/ cold impact of -40°/ -35°C in accordance with CSA 22.2 No. 0.3
    • Flame retardant in accordance with IEEE 1202 and IEC 60332-3-22 Category A
    • Arctic neoprene jacket allows ease of stripping in all temperatures
    • Meets IEEE standards for 2000V and performance requirements of IEC standards for 0.6/1kV
    • This product may be manufactured in an unarmored or armored and sheathed version
    • Armored and sheathed cables suitable for use in Class 1 Division 1 and Zone 1 hazardous locations offshore
    • Unarmored cables suitable for use in Class I, Division 2 hazardous locations offshore
    • Meets requirements for UL 1277 Type TC-ER for exposed runs

    unarmored
    conductor
    size
    type
    designation
    ground
    size
    sheath
    thickness
    cable
    diameter
    (nominal)
    inductance capacitance calculated
    ampacity†
    (measured @ ºc)
    cable weight
    (approximate)
    draka cable
    part number
    awg/
    mcm
    mm2 awg/
    mcm
    mm2 in mm in mm Ω/kft Ω/km pf/ft pf/m 95 100 110 125* lbs/
    mft
    kg/km
    1/0 56.3 tp(obs)n-1/0 5 18.6 n/a n/a 1.520 38.6 0.09 0.3 190 623 156 164 176 229 2275 3385 036028
    2/0 66.5 tp(obs)n-2/0 4 21.5 n/a n/a 1.620 41.1 0.09 0.3 212 695 175 186 201 254 2730 4065 036029
    4/0 112.6 tp(obs)n-4/0 1 56.3 n/a n/a 2.090 53.1 0.09 0.3 259 850 241 252 270 354 4360 6490 036030
    262 133.0 tp(obs)n-262 1 56.3 n/a n/a 2.220 56.4 0.09 0.3 247 810 267 294 315 395 5045 7510 036031
    313 158.6 tp(obs)n-313 110 18.6 n/a n/a 2.350 59.7 0.08 0.2 270 886 298 321 344 442 5855 8715 036032
    373 189.3 tp(obs)n-373 210 61.5 n/a n/a 2.540 64.5 0.08 0.2 292 958 333 361 387 492 6950 10345 036033
    444 225.1 tp(obs)n-444 310 92.1 n/a n/a 2.850 72.4 0.08 0.2 318 1043 371 411 440 608 8650 12875 036034
    535 271.2 tp(obs)n-535 310 92.1 n/a n/a 3.010 76.5 0.09 0.3 291 954 417 443 475 608 9695 14430 036035
    646 327.5 tp(obs)n-646 410 112.6 n/a n/a 3.160 80.3 0.09 0.3 314 1030 469 516 553 678 11395 16960 036036
    777 393.8 tp(obs)n-777 262 133.0 0.060 1.5 3.500 88.9 0.09 0.3 345 1132 528 582 602 750 13515 20115 036037

    armored and sheathed
    conductor
    size
    type
    designation
    ground
    size
    sheath
    thickness
    cable
    diameter
    (nominal)
    inductance capacitance calculated
    ampacity†
    (measured @ ºc)
    cable weight
    (approximate)
    draka cable
    part number
    awg/
    mcm
    mm2 awg/
    mcm
    mm2 in mm in mm Ω/kft Ω/km pf/ft pf/m 95 100 110 125* lbs/
    mft
    kg/km
    1/0 56.3 tp(obs)nbs-1/0 5 18.6 0.110 2.8 1.800 45.7 0.09 0.3 190 623 156 164 176 229 2275 3385 036038
    2/0 66.5 tp(obs)nbs-2/0 4 21.5 0.110 2.8 1.900 48.3 0.09 0.3 212 695 175 188 201 254 2730 4065 036039
    4/0 112.6 tp(obs)nbs-4/0 1 56.3 0.110 2.8 2.370 60.2 0.09 0.3 259 850 241 252 270 354 4360 6490 036040
    262 133.1 tp(obs)nbs-262 1 56.3 0.110 2.8 2.500 63.5 0.09 0.3 247 810 267 294 315 395 5045 7510 036041
    313 158.7 tp(obs)nbs-313 110 18.6 0.110 2.8 2.630 66.8 0.08 0.2 270 886 298 32 344 442 5855 8715 036042
    373 189.2 tp(obs)nbs-373 210 61.5 0.140 3.6 2.880 73.2 0.08 0.2 292 958 333 361 387 492 6950 10345 036043
    444 225.2 tp(obs)nbs-444 310 92.1 0.140 3.6 3.190 81.0 0.08 0.2 318 1043 371 411 440 594 8650 12875 036044
    535 271.3 tp(obs)nbs-535 310 92.1 0.140 3.6 3.350 85.1 0.09 0.3 291 954 417 443 475 608 9695 14430 036045
    646 327.5 tp(obs)nbs-646 410 112.6 0.140 3.6 3.530 89.7 0.09 0.3 314 1030 469 516 553 678 11395 16960 036046
    777 394.2 tp(obs)nbs-777 262 133.0 0.140 3.6 3.840 97.5 0.09 0.3 345 1132 528 582 602 750 13515 20115 036047

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours

    Captcha Image

    This product has no related products.

Request a Quote

Receive A Response In 5 Minutes Or Less During Business Hours

Sign up for our newsletter

Register with Nassau today.

Subscribe to Newsletter