Prysmian and Draka Cable 6 AWG Bostrig Type P Single Conductor Armored and Sheathed 600V Power Cable T26025

Prysmian and Draka Cable 6 AWG Bostrig Type P Single Conductor Armored and Sheathed 600V Power Cable T26025

Select gauge from drop-down menu for prices:

Prysmian and Draka Cable 6 AWG Bostrig Type P Single Conductor Armored and Sheathed 600V Power Cable T26025
Prysmian and Draka Cable 6 AWG Bostrig Type P Single Conductor Armored and Sheathed 600V Power Cable T26025

Conductor: Soft annealed stranded tinned copper nper ASTM B 33. A polyester tape separator is used over the conductor. 

Insulation: Bostrig Type P chemically cross-linked polyolefin (XLPO), meeting IEEE 1580. Thickness as shown in tables on opposite page. 

Armor: Braided bronze in accordance with IEEE 1580. 

Sheath: Flame-Retardant Thermosetting CPE (Chlorinated Polyethylene) applied over the armor in accordance with the requirements of IEEE-1580-2010. Thickness as shown in tables on opposite page. Arctic Neoprene (Type N) also available as an option. 

Applications: 
• Bostrig™ Type P Marine and Offshore Cable is primarily designed for power, control, signal, and instrumentation applications for offshore and land drilling rigs, marine vessels, and offshore production facilities. 
• Bostrig™ cables have excellent resistance to oil, abrasion, moisture, vibration, sunlight, and ester based mud (Type P- MR). They are suitable for use in Class 1, Division 1 offshore applications (armored & sheathed). 
• The standard insulation has a continuous operating temperature of 125°C, allowing for higher ampacity levels. These cables also meet cold bend requirements of -40°C and cold impact of -35°C (CSA 22.2 N0. 0.3). 
• This product may be manufactured in an unarmored or armored and sheathed version. 

Approvals:
• IEEE 1580 and IEEE 45- Marine Shipboard Cable 
• UL 1309- Marine Shipboard Cable Type X110 
• CSA 22.2 No. 245- Marine Shipboard Cable Type X110 
• Det Norske Veritas (DNV) 
• American Bureau of Shipping (ABS) 
• Transport Canada Approved AMS400-20-2 
• Transport Canada 8700-20-2 
• Lloyd’s Register of Shipping (LRS) 
• United States Coast Guard-46CFR 

Features/Ratings: 
• Superior resistance to oil, abrasion, moisture, sunlight, crush and impact 
• High strand count conductors provide superior flexibility 
• Higher allowable conductor operating temperature results in increased ampacity 
• Cold bend/ cold impact of -40°/ -35°C in accordance with CSA 22.2 No. 0.3 
• Flame retardant in accordance with IEEE 1202 and IEC 60332-3-22 Category A 
• Meets IEEE standards for 600V and performance requirements of IEC standards for 0.6/1 kV
• Armored and sheathed cables suitable for use in Class 1
• Division 1 and Zone 1 hazardous locations offshore

technical specification:
conductor size awg/mcm 6
conductor size mm² 12.5
sheath thickness in 0.060
sheath thickness mm 1.5
cable diameter (nominal) in
0.480
cable diameter (nominal) mm
12.2
impedance (phase-neutral) ω/kft
0.5
impedance (phase-neutral) ω/km 1.6
inductance (mh/kft) 0.12
inductance (mh/km) 0.4
capacitance (pf/ft) 126
capacitance (pf/m) 413
ampacity measured @ 95ºc
90
ampacity measured @ 100ºc 96
ampacity measured @110ºc 103
ampacity measured @ 125ºc
126
cable weight approximate (lbs/mft) 205
cable weight approximate (kg/km) 305
type designation SPBS-6
prysmian and draka cable number T26025

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question