• Amercable Arctic Grade CIR Type VFD Power Cable UL Listed as Type TC-ER & Type TC-ER-HL 3/C Gexol Ins. 2kV Rated 90C 37-102 CIRVFDA

    Product Details

    Power Conductors (x3): Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.

    Ground Conductors (x3): Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11. Gexol® insulation sized per UL 1277. Color: Green

    Insulation (2kV): Gexol® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. Color: Gray with printed phase I.D. (Black-Red-Blue)

    Shield: Overall tinned copper braid plus aluminum/polyester tape providing 100% coverage.

    Jacket: A black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset CPE meeting UL 1309/CSA 245 and IEEE 1580.

    Safer to Handle: CIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors

    CIR® Ratings & Approvals:
    • 90°C temperature rating
    • UL Listed as Marine Shipboard Cable (E111461)
    • UL Listed as Type TC-ER
    • UL Listed as TC-ER-HL (cables up to 1” in diameter)
    • American Bureau of Shipping (ABS)
    • Flame Retardant – IEEE 1202
    • Suitable for use in Class I, Div 2 and Zone 2 environments
    • Suitable for Class 1, Div 1 and Zone 1 environments. (cables less than 1” in OD)

    Application: A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications.

    Features:
    • Specially engineered cable design produces a longer cable life in VFD applications in severe cold environments.
    • Exceeds CSA cold bend/cold impact (-40°C/-35°F)
    • Brittlepoint as per ASTM D 7646-07 exceeds -65°C for Jacket and -75°C for insulation
    • Overall braid and foil shield provides 100% coverage containing VFD EMI emissions.
    • Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive.
    • High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
    • Gexol’s lower dielectric constant (standard XLPEs,EPRs and other Type P insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system.
    • 2kV insulation thickness resists the repetitive 2x voltage spikes from 600V VFDs and reduces drive over current trip problems due to cable charging current.
    • Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL
    • Gas & vapor tight – impervious to water and air
    • Smaller bend radius (up to 40% smaller) than Type MC
    • Considerably more flexible than Type MC
    • Reduced installation time and cost compared to Type MC
    • Glands cost up to 50% less

    size
    awg/
    kcmil
    nominal
    diameter
    inches*
    weight
    per
    1000 ft.
    dc resist.
    @ 25°c
    (ohms/1k ft)
    ac resist.
    @ 90°c, 60 hz
    (ohms/1k ft)
    inductive
    reactance
    (ohms/1k ft)
    voltage drop
    @ 90°c
    (volts/amp/
    1k ft)
    green insulated
    grounding
    size (awg)
    ieee
    amp.
    90°c
    nec
    amp.
    90°c
    ieee
    amp.
    75°c
    nec
    amp.
    75°c
    amercable
    part number
    14 0.742 283 2.907 3.635 0.040 5.073 18 24 15 20 15 37-102-508cirvfda
    12 0.815 378 1.826 2.283 0.038 3.199 18 29 20 24 20 37-102-516cirvfda
    10 0.871 473 1.153 1.441 0.036 2.032 14 38 30 32 30 37-102-308cirvfda
    8 0.893 553 0.708 0.885 0.037 1.263 14 48 55 41 50 37-102-309cirvfda
    6 1.093 797 0.445 0.556 0.033 0.804 12 65 75 54 65 37-102-310cirvfda
    4 1.225 929 0.300 0.376 0.031 0.552 12 83 95 70 85 37-102-312cirvfda
    2 1.341 1276 0.184 0.230 0.029 0.348 10 111 130 93 115 37-102-314cirvfda
    1 1.447 1576 0.147 0.184 0.029 0.285 10 131 145 110 130 37-102-315cirvfda
    1/0 1.566 2144 0.117 0.147 0.029 0.234 10 150 170 126 150 37-102-316cirvfda
    2/0 1.733 2144 0.093 0.117 0.028 0.192 10 173 195 145 175 37-102-317cirvfda
    4/0 1.874 3131 0.058 0.075 0.027 0.132 8 232 260 194 230 37-102-319cirvfda
    262 2.031 3875 0.048 0.063 0.027 0.115 6 273 297 228 262 37-102-320cirvfda
    313 2.130 4709 0.040 0.053 0.026 0.100 6 298 328 249 292 37-102-321cirvfda
    373 2.257 5209 0.034 0.045 0.025 0.088 6 332 364 277 322 37-102-322cirvfda
    444 2.400 6310 0.028 0.039 0.025 0.080 6 382 402 319 355 37-102-323cirvfda
    535 2.705 7193 0.024 0.033 0.026 0.072 6 407 446 340 394 37-102-324cirvfda
    646 2.898 9217 0.020 0.028 0.026 0.065 4 474 496 396 438 37-102-326cirvfda
    777 3.102 10340 0.016 0.025 0.025 0.060 4 516 546 431 483 37-102-327cirvfda

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours

    Captcha Image

    This product has no related products.

    NOW VIEWING

    Amercable Arctic Grade CIR Type VFD Power Cable UL Listed as Type TC-ER & Type TC-ER-HL 3/C Gexol Ins. 2kV Rated 90C 37-102 CIRVFDA

    Request a Quote

Request a Quote

Receive A Response In 5 Minutes Or Less During Business Hours

Sign up for our newsletter

Register with Nassau today.

Subscribe to Newsletter