Amercable Type SH 4/0 AWG Single Conductor 25kv 90C Mobile Substation Power Cable 37-550-033

Amercable Type SH 4/0 AWG Single Conductor 25kv 90C Mobile Substation Power Cable 37-550-033

Select gauge from drop-down menu for prices:

Amercable Type SH 4/0 AWG Single Conductor 25kv 90C Mobile Substation Power Cable 37-550-033
Amercable Type SH 4/0 AWG Single Conductor 25kv 90C Mobile Substation Power Cable 37-550-033

Conductor: Flexible tin-coated soft annealed bunch stranded copper meeting ASTM B-33 

Conductor Shield: Combination semi-conducting tape and/or extruded semiconductive thermosetting material 

Insulation: Heat, moisture and ozone resisting 90°C Ethylene- Propylene rubber (EPR) meeting ICEA S-75- 381/NEMA WC58 

Insulation Shield: Tin-coated copper braid applied over a semiconductive tape (5-15kV). Extruded semi-conductive thermosetting material (25-35kV) 

Jacket: CPE meeting ICEA S-75-381/NEMA WC58. Consult factory for availability of other jacket materials. 

Identification: Cable shall be surface printed showing manufacturer, size, voltage rating, type and temperature rating 

Application: These single conductor portable power cables are extremely flexible and specifically designed for use on mobile substation equipment. The Type SH cable is often necessary for supplying power while replacing damaged utility poles or during routine maintenance of substations. 

Features: 
• Extremely flexible stranding for ease of bending 
• The conductor shield is bonded to the insulation – providing easy, clean stripping 
• Jacket is heat, oil, flame and chemical resistant 
• Continuous conductor temperature 90°C 
• Jackets available in voltage colors, yellow (5 & 8kV), orange (15kV), red (25 & 35kV). Consult factory for availability of other colors. 

Ratings & Approvals: 
• ASTM B-33: Standard Specification for Tinned Soft or Annealed Copper Wire for Electrical Purposes 
• ICEA S-75-381/NEMA WC-58: Portable and Power Feeder Cables for Use in Mines and Similar Applications 
• UL 1072 Medium Voltage Cable MV-105 (pending)

technical specification:
size awg/kcmil 4/0
minimum wires per conductor 532
nominal insulation thickness in. .295
nominal jacket thickness in. .190
nominal outside diameter in. 1.713
approx.weight lbs. per 1,000 ft. 1909
ampacity 90°c 395
amercable part number 37-550-033

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question