Prysmian Cable 2 Solid 5kV 100% Aluminum EPR DOUBLESEAL Single Phase Full Neutral Medium Voltage Utility Cables QJL030A

Prysmian Cable 2 Solid 5kV 100% Aluminum EPR DOUBLESEAL Single Phase Full Neutral Medium Voltage Utility Cables QJL030A

Select gauge from drop-down menu for prices:

Prysmian Cable 2 Solid 5kV 100% Aluminum EPR DOUBLESEAL Single Phase Full Neutral Medium Voltage Utility Cables QJL030A
Prysmian Cable 2 Solid 5kV 100% Aluminum EPR DOUBLESEAL Single Phase Full Neutral Medium Voltage Utility Cables QJL030A

Conductors: Solid or Class B Compressed concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM. Stranded conductors are water-blocked with STRANDSEAL® conductor filling compound.

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation: Natural high dielectric strength EPROTENAX™ EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life.

Insulation Shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metallic Shield: Solid bare copper wires, helically applied and uniformly spaced. Water-blocking agents applied over the insulation shield and around the neutral wires to prevent longitudinal water penetration.

Jacket: Black insulating sunlight resistant linear low density polyethylene encapsulating the neutral wires with three extruded red stripes and NESC lightning bolt symbol.

Description: Single conductor cable with solid or filled strand aluminum or copper conductors, triple extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, copper concentric neutral wires, water swellable agents, black encapsulating linear low-density polyethylene (LLDPE) jacket.

Options:
• Black LLDPE jacket with no stripes
• Multiplex cables
• Tinned round and flat strap neutrals
• Compact stranded conductors
• UL MV-90 rating if required
• 46kV
• RUS Bulletin 1728F-U1 where applicable

Installation:
• Conduit In Air
• Direct Buried
• Underground Duct
• Isolated In Air
• Wet Locations
• Dry Locations
• With Messenger
• Utility Primary

Specifications and ratings:
• AEIC- AEIC CS8
• ICEA- ICEA S-94-649
• ICEA- ICEA T-31-610
• ICEA- ICEA T-34-664
• For 105°C continuous, 140°C emergency, 250°C short-circuit operation

technical specifications:
conductor 2 Solid al
insulation thickness (mils) 90
concentric neutral 10-#14
conductor diameter (in) - (a) 0.258
insulation diameter (in) - (b) 0.49
insulation shield diameter (in) - (c) 0.56
jacket diameter (in) - (d) 0.80
cable weight (lbs/kft) 377
minimum bending radius (in) 7
† ampacity (amps) - ‡105°c in duct 130
+/- sequence impedance resistance (µΩ/ft) - ‡105°c in duct 694
+/- sequence impedance reactance (µΩ/ft) - ‡105°c in duct 24
zero sequence impedance resistance (µΩ/ft)†† - ‡105°c in duct 694
zero sequence impedance reactance (µΩ/ft)†† - ‡105°c in duct 25
† ampacity (amps) - ‡105°c direct buried 182
+/- sequence impedance resistance (µΩ/ft) - ‡105°c direct buried 694
+/- sequence impedance reactance (µΩ/ft) - ‡105°c direct buried 24
zero sequence impedance resistance (µΩ/ft)†† - ‡105°c direct buried 694
zero sequence impedance reactance (µΩ/ft)††- ‡105°c direct buried 25
prysmian cable part number QJL030A

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question