General Cable EmPowr® 750kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils

General Cable EmPowr® 750kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils

Select gauge from drop-down menu for prices:

General Cable EmPowr® 750kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils
EmPowr 750kcmil 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation 175 mils

Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97- 682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable. 

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum. 

Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer. 

Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III. 

Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation. 

Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator. 

Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC). 

Features and Benefits: 
• Triple-extruded for clean interfaces 
• Class 10,000 environment utilized for cable core material handling 
• Flexibility for easy handling 
• Excellent moisture resistance 
• Deformation-resistant 
• High dielectric strength 
• Low dielectric loss 
• Excellent resistance to water treeing 
• Clean-stripping insulation shield without the use of a release agent 
• Sunlight-resistant 

Temperature Rating: 
• Normal - 105°C 
• Emergency* - 140°C 
• Short Circuit - 250°C

Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried. 

Options: 
• Copper conductors 
• EmPowr® Fill LF Lead-Free EAM 
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610 
• Dry nitrogen cure 
• True Triple Extrusion 
• 3 X 1/C triplex or parallel 
• Type MV-105 UL 1072 
• UL Listedb

technical specifications:
compressed conductor(al awg or kcmil) 750
compressed conductor(no.of wires) 61
copper neutral(no.of wires) 7
copper neutral(wire size awg)
20
diameter (1) inches (min. insulation ) 1.340
diameter (1) inches (max. insulation) 1.425
diameter (1) inches (pvc jacket) 1.664
nominal jacket thkn. inches (1) 0.080
approx. weight (1) lb/1000 ft(al cond.) 703
approx. weight (1) lb/1000 ft(cu shield) 23
approx. weight (1) lb/1000 ft(total)
1422
ampacity (2)(directburied) 660
ampacity (2)(in duct) 510

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question