• EmPowr 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation

    Product Details

    Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97- 682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable. 

    Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum. 

    Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer. 

    Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III. 

    Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation. 

    Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator. 

    Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC). 

    Features and Benefits: 
    • Triple-extruded for clean interfaces 
    • Class 10,000 environment utilized for cable core material handling 
    • Flexibility for easy handling 
    • Excellent moisture resistance 
    • Deformation-resistant 
    • High dielectric strength 
    • Low dielectric loss 
    • Excellent resistance to water treeing 
    • Clean-stripping insulation shield without the use of a release agent 
    • Sunlight-resistant 

    Temperature Rating: 
    • Normal - 105°C 
    • Emergency* - 140°C 
    • Short Circuit - 250°C

    Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried. 

    Options: 
    • Copper conductors 
    • EmPowr® Fill LF Lead-Free EAM 
    • STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610 
    • Dry nitrogen cure 
    • True Triple Extrusion 
    • 3 X 1/C triplex or parallel 
    • Type MV-105 UL 1072 
    • UL Listedb

    compressed
    conductor
    copper
    neutral
    diameter (1)
    inches
    nominal
    jacket
    thkn.
    inches(1)
    approx. weight (1)
    lb/1000 ft
    ampacity (2)
    al
    awg/
    kcmil
    no.
    of
    wires
    no.
    of
    wires
    wire
    size
    awg
    insulation
    pvc
    jacket
    al
    cond.
    cu
    shield
    /wires
    total
    direct
    buried
    in
    duct
    min. max.
    175 mils nominal epr insulation – 15 kv 100% level
    2 7 9 24 0.635 0.720 0.937 0.080 62 12 388 165 125
    1 19 6 22 0.675 0.760 0.987 0.080 78 13 424 190 145
    1/0 19 7 22 0.715 0.800 1.027 0.080 99 15 468 215 165
    2/0 19 7 22 0.760 0.845 1.071 0.080 125 15 517 245 185
    3/0 19 7 22 0.810 0.895 1.121 0.080 158 15 576 280 215
    4/0 19 8 22 0.865 0.950 1.177 0.080 199 17 649 320 245
    250 37 8 22 0.920 1.005 1.233 0.080 234 17 716 355 275
    350 37 9 22 1.015 1.100 1.336 0.080 329 19 868 430 335
    500 37 6 20 1.150 1.235 1.477 0.080 468 20 1080 525 410
    750 61 7 20 1.340 1.425 1.664 0.080 703 23 1422 660 510
    1000 61 8 20 1.485 1.575 1.873 0.110 937 27 1840 765 615
    220 mils nominal epr insulation – 15 kv 133% level
    2 7 9 24 0.725 0.815 1.027 0.080 62 12 457 165 125
    1 19 7 22 0.765 0.855 1.077 0.080 78 15 498 190 145
    1/0 19 7 22 0.805 0.895 1.117 0.080 99 15 543 215 165
    2/0 19 8
    22 0.850 0.935 1.161 0.080 125 17
    597 245 185
    3/0 19 8 22 0.900 0.985 1.211 0.080 158 17
    660 280 215
    4/0 19 8 22 0.955 1.045 1.267 0.080 199 17
    735 320 245
    250 37 9 22 1.010 1.100 1.323 0.080 234 19
    808 350
    275
    350 37 6 20
    1.105 1.190 1.439 0.080 329 20
    968 425
    335
    500 37 7 20 1.240 1.330 1.567 0.080 468 23
    1189 520
    410
    750 61 8 20 1.430 1.520 1.814 0.110 703 27
    1641 655
    510
    1000 61 9 20 1.575 1.670 1.963 0.110 937 30
    1979 765
    615

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours

    Captcha Image

    This product has no related products.

    NOW VIEWING

    EmPowr 15 kV Copper Wire PVC Jacket Fill Shielded Power Cable Al Conductor EPR Insulation

    Request a Quote

Request a Quote

Receive A Response In 5 Minutes Or Less During Business Hours

Sign up for our newsletter

Register with Nassau today.

Subscribe to Newsletter