General Cable PowrServ® OH Duplex 1/0 AWG Malemute/XP 500 Feet Al Conductor XLPE Insulation Service Drop Cable Neutral-Supported 600V

General Cable PowrServ® OH Duplex 1/0 AWG Malemute/XP 500 Feet Al Conductor XLPE Insulation Service Drop Cable Neutral-Supported 600V

Select gauge from drop-down menu for prices:

General Cable PowrServ® OH Duplex 1/0 AWG Malemute/XP 500 Feet Al Conductor XLPE Insulation Service Drop Cable Neutral-Supported 600V
PowrServ OH Duplex 1/0 AWG Malemute/XP 500 Feet Al Conductor XLPE Insulation Service Drop Cable Neutral-Supported 600V

Complete Cable: Overhead (OH) duplex service drop cable consists of one aluminum conductor insulated with extruded lead-free Cross-linked Polyethylene (XLPE), twisted around a bare conductor which serves as a supporting neutral. Service drop cable meets the requirements of ANSI/ICEA S-76-474.

Insulated Conductors: The all-aluminum stranded conductors are Class A, Class B, or SIW compressed 1350-H19 aluminum. Solid conductors are H16 temper.

Insulation: The insulation is black extruded lead-free Cross-linked Polyethylene (XLPE).

Bare Neutral: The all-aluminum stranded conductors are Class AA or Class A 1350-H19 (AAC) or 6201- T81 alloy (AAAC). The aluminum conductor steel reinforced (ACSR) is Class AA. The direction of lay of the outer layer is right-hand.

Phase Identification: Phase identification is provided by means of white print legend markings on the phase conductor.

Features and Benefits: The insulated conductors of service drop cables are resistant to weathering, sunlight, abrasion, tearing, cutting and chemicals. This cable is rated at 600 volts with a maximum conductor operating temperature of 90°C for cross-linked polyethylene insulation.

Applications: Duplex service drop cable is intended to deliver single phase power from the secondary power line or pole mounted transformer to the serviceentrance conductors at the user’s building or other structure. It may also be used as pole line secondary with service splices at the pole or in mid-span.

Options:
• Aluminum 1350-H16 or H26 (¾ Hard) conductor
• Copper conductors
• High-molecular-weight Polyethylene (PE) insulation, 75°C rating
• High-Density Polyethylene (HDPE) insulation, 75°C rating
• MasterPak® reel-less packaging

technical specification:
phase conductor(size awg) 1/0
phase conductor(no. of wires(1)) 19
phase conductor(ins. thkn.inches) 0.060
neutral conductor(size awg) 1/0
neutral conductor(no. of wires) 7
neutral conductor(rated strg.pounds) 1990
eff. o.d.inches 0.84
approx. weight lb/1000ft(al) 199
approx. weight lb/1000ft(total) 233
amps (2) 260
packaging (3)(type & size) NR 32.24
packaging (3)(length feet) 500
code word Malemute/XP