FLEXIBLE AND FLAME 535KCMIL 8 KV RETARDANT MV-RIG 115 MILS TYPE E MEDIUM VOLTAGE VFD POWER CABLE THREE CONDUCTOR UNARMORED

Conductor: 6 AWG thru 777 kcmil fully annealed flexible tinned copper

Conductor Shield: Semi-conducting tape and extruded semi-conducting material 

Insulation: Thermoset 90°C Ethylene Propylene Rubber – Type E 

Insulation Shield: Extruded semi-conducting material and semi-conducting tape 

Metallic Shield: A composite braid consisting of tinned copper/colored nylon – Black, Blue, Red 

Ground: 3 green covered tinned copper grounding conductors 

Shield: Overall tinned copper braid with aluminum/polyester tape – 100% coverage for shield effectiveness 

Sheath: Black Thermoset Chlorinated Polyethylene – Type XL-CPE 

Options: 
• Colored sheaths available upon request: 8 kV Orange, 15 kV Red 
• Bronze braid armor, 88% minimum coverage with overall Type XL-CPE sheath 

Applications: 
• AC motor Variable Frequency Drives (VFD) 
• Offshore oil and gas drilling and production platforms requiring medium voltage 
• Mobile offshore drilling units and production platforms 
• Fixed and floating offshore production platforms 
• Commercial ships 
• Suitable for use in Class I, Division 2 per API-RP14F 

Features: 
• Premium medium-voltage power cable for distribution 
• Excellent flame resistance 
• Flexible for easy handling 
• Faster and easier to install 
• Meets cold bend test at -40?C per UL 1309 and IEEE 1580 
• Meets cold impact test at -35?C per IEEE 1580 

Compliances: 
Industry: 
• API-RP14F 
• CSA C22.2 No. 245 Type E90 
• ICEA S-93-639 
• IEEE 1580 Type E 
• UL 1072 
• UL 1309 Type E90 
• Mud oil-resistant 
• IEC 61892-4 

Flame Test: 
• IEEE 1202 
• IEC 60332-3-22 Cat. A 
• CSA C22.2 No. 245 
• UL 1309

technical specification:
cond. size(awg) 535
no. of cond. 3
grounding cond. size(awg) 3—#5
nominal cable diameter(inches) 3.111
nominal cable diameter(mm) 79.03
net weight(lbs/1000 ft) 8850
net weight(kg/km) 13171
ampacity* in free air @ 45?c ambient(90?c) 528
catalog number 24320.036600