Prysmian and Draka Cable 3/0 AWG Bostrig Type P Five Conductor Unarmored 600V Power Cable T26106

Prysmian and Draka Cable 3/0 AWG Bostrig Type P Five Conductor Unarmored 600V Power Cable T26106

Prysmian and Draka Cable 3/0 AWG Bostrig Type P Five Conductor Unarmored 600V Power Cable T26106

Conductors: Soft annealed stranded tinned copper per ASTM B 33. A polyester tape separator is used over the conductor.

Insulation: Bostrig Type P chemically cross-linked polyolefin (XLPO), meeting IEEE 1580.

Jacket: Flame-Retardant Thermosetting CPE (Chlorinated Polyethylene) applied over the armor in accordance with the requirements of IEEE-1580-2010. Thickness as shown in tables on opposite page. Arctic Neoprene (Type N) also available as an option.

Applications:
• Bostrig™ Type P Marine and Offshore Cable is primarily designed for power, control, signal, and instrumentation applications for offshore and land drilling rigs, marine vessels, and offshore production facilities.
• Bostrig™ cables have excellent resistance to oil, abrasion, moisture, vibration, sunlight, and ester based mud (Type P- MR). They are suitable for use in Class 1, Division 1 offshore applications (armored & sheathed).
• The standard insulation has a continuous operating temperature of 125°C, allowing for higher ampacity levels. These cables also meet cold bend requirements of -40°C and cold impact of -35°C (CSA 22.2 N0. 0.3).
• This product may be manufactured in an unarmored or armored and sheathed version.

Features/Ratings:
• Superior resistance to oil, abrasion, moisture, sunlight, crush and impact
• High strand count conductors provide superior flexibility
• Higher allowable conductor operating temperature results in increased ampacity
• Cold bend/ cold impact of -40°/ -35°C in accordance with CSA 22.2 No. 0.3
• Flame retardant in accordance with IEEE 1202 and IEC 60332-3-22 Category A
• Meets IEEE standards for 600V and performance requirements of IEC standards for 0.6/1 kV
• Unarmored cables suitable for Class 1, Division 2 and Zone 2 hazardous locations offshore
• Meets the requirements of UL 1277 and UL 1569 for Type TC-ER exposed runs

Approvals:
• IEEE 1580 and IEEE 45- Marine Shipboard Cable
• UL 1309- Marine Shipboard Cable Type X110
• CSA 22.2 No. 245- Marine Shipboard Cable Type X110
• CSA 22.2 No. 230- Type TC-ER
• CSA 22.2 No. 230 & No. 38 Direct Burial (#14 AWG & larger)
• Det Norske Veritas (DNV)
• American Bureau of Shipping (ABS)
• Transport Canada Approved AMS400-20-2
• Transport Canada 8700-20-2
• Lloyd’s Register of Shipping (LRS)
• United States Coast Guard-46CFR

technical specification:
conductor size awg/mcm 3/0
conductor size - mm² 92.1
sheath thickness - in 0.110
sheath thickness - mm 2.8
cable diameter (nominal) - in 2.060
cable diameter (nominal) - mm 52.3
impedance (phase-neutral) - Ω/kft 0.08
impedance (phase-neutral) - Ω/km 0.3
inductance (mh/kft) 0.09
inductance (mh/km) 0.3
capacitance (pf/ft) 245
capacitance (pf/m) 804
calulated ampacity† (measured @ 95ºc) 170
calulated ampacity† (measured @ 100ºc) 174
calulated ampacity† (measured @ 110ºc) 187
calulated ampacity† (measured @ 125ºc) 250
cable weight approximate (lbs/mft) 3,995
cable weight approximate (kg/km) 5,945
type designation qpn-3/0
prysmian and draka cable part number T26106

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question